User Manual

Building Operator Engineering Guide
Setting Up Connect Device and Building Operator
20 | 69
A6V11881627_en_k
1. Select the Network tab. Then, select the Firewall header.
2. Create the following inbound rules for:
Separate Network Mode
Description
Protocol
Source Port
Destination
Interface
Target
Modbus
devices
tcp
502
lan0
accept
BACnet IP
devices
udp
47808
lan0
accept
Building
Operator
Discovery
Web-client
tcp
8085
lan0
accept
Default
all
RETURN
Single Network Mode
Description
Protocol
Source Port
Destination
Interface
Target
Modbus
devices
tcp
502
wan0
accept
BACnet IP
devices
udp
47808
wan0
accept
Building
Operator
Discovery
Web-client
tcp
8085
wan0
accept
Default
all
RETURN
Protocol entries only accept lowercase letters.
Depending on building automation network configuration on site, the source ports
may differ.
Select Accept from the Target drop-down for each rule. Select Add to confirm.
You can create outbound rules by clicking the Outbound Rule tab. However,
outbound rules do not need to be configured.
1.2.7 Enabling remote web access in Connect device UI
To use remote web access, you must configure your endpoints in the Connect
Device. For example, to remote web access to on-premise Desigo CC Flex Client,
you must enter to IP address of the Flex web application in the Connect Device UI.
To configure your endpoints, follow the steps below.
In the Connect Device UI: