User Manual
Building Operator Engineering Guide
Configuring Alarms in Building Operator Discovery
1
A6V11881627_en_k
55 | 69
The values you apply in this window will be written to the points selected in the
Alarm Config list.
1.4.1 Configuring Number Alarm
When configuring a Number alarm with a Delta From Setpoint value, follow the
instructions below:
1. Open and launch Alarm Config from the Building Operator Discovery
applications menu.
2. Select the Number point filter, select Number Alarm in the Alarm Configuration
drop-down, then select Add/Edit.
3. In the pop-up, change the value(s) in the fields provided to meet the
parameters for your point alarm. In the Compare Point Name field, copy and
paste the NavName of the point you want to compare to. The point you want to
compare to, must exist within the same equip as the point the alarm is being
configured for.
The Compare Point Name field is case sensitive.
4. Select OK when finished.