Adding Data Points Using Building Operator Discovery
1
46 | 66
A6V11881627_en_i
4. After the selecting the data point, use the icons at the top of the chart to toggle
between the line and bar chart options.
When selecting the Year view, you can switch between monthly and hourly
aggregation levels.
1.3.8 Determining BACnet Write Priority for Points
BACnet priorities are vary for different vendors. Siemens devices abide by the
following BACnet priority array:
● 1-6: Safety and protection
● 7: Delay time on/off
● 8: Manual operation
● 9-16: Program mode
If you want Building Operator to write to any value or output with a BACnet priority
array, you must determine a write level. Building Operator Discovery has its own
priority array, but it’s important to set the BACnet write level appropriately for the
end device.
Complete the following instructions to configure the write priority for BACnet points:
Changing Point Priority Individually