User Manual
Building Operator Engineering Guide
Adding Data Points Using Building Operator Discovery
1
A6V11881627_en_i
47 | 66
1. Find and select the appropriate value or output point beneath the device, in the
Available Equip tree.
2. In the point editor, find the Write Level field.
3. Use the up or down arrows, or type to enter 8 for the field value. Any command
you send to the Building Operator Discovery priority array will be sent out to the
end BACnet device at slot 8, or manual override.
4. Select Save at the bottom of the editor to save your changes.
1.3.9 Restarting Connect Device to Update Data Point
Information
If you want to update data point information or change it for any reason, you’re able
to do so in Building Operator Discovery.
However, any data point information you update in Building Operator Discovery
won’t appear in Building Operator until there’s a change of value (COV) on that
specific data point. To force a COV, as an Administrator, you must restart the
Connect device. The example below outlines how to restart the gateway to force a
COV.
To restart the Connect device to update data points:
1. Navigate to the point you want to change in the Available Equip Tree (Site >
Floor > Equipment > Data point) and type to enter the revisions in the
appropriate field(s). In this example, we’re adding
“(SieSte20)”
to the end of the
AOV2 data point name.
2. Select Apply when finished.
3. In a separate browser tab, log in to Connect device. Use the same username
and password you created earlier when you first activated the device.
4. Select the Maintenance tab in the navigation ribbon.