Configuring Alarms in Building Operator Discovery
1
56 | 66
A6V11881627_en_i
9. Select OK to proceed.
1.4.3 Configuring Multistate Alarm State Text
If you’re configuring a Multistate alarm that has multiple values, you need to know
which of these values to manually add to trigger an alarm.
To determine this, please complete the instructions below:
1. Open and launch DB Builder from the Building Operator Discovery applications
menu.
2. Navigate to and select the multistate point on the appropriate device.
3. Find and select the information icon (i), above the Point Name field. Scroll
down to find the enum property. To the right, you’ll find the Multistate point
values, listed in ascending order (0, 1, 2, 3, 4, etc.).
4. Once you’ve determined which value(s) you’d like to manually add, navigate to
the Alarm Config application.