1.6 System Limits
For ideal performance, ensure that your system is configured with the following
limitations in mind:
● Maximum number of data points per Connect device: 500
● Maximum number of COVs per Connect device: 200/minute
● Maximum number of alarms per Connect device: 200/minute
For devices that do not support COVs, Building Operator Discovery will poll the
network according to its default tuning policy. On slow networks, such as MSTP,
this tuning policy may not be ideal. Refer to the Building Operator Discovery
documentation for instructions to configure a custom tuning policy
BACnet Objects
The current Building Operator Discovery is not BTL listed, however, you can
represent nine basic object types within Building Operator. More object types will
be available once certification is obtained.
Analog Input
Analog Output
Analog Value
Binary Input
Binary Output
Binary Value
Multi-State Input
Multi-State Output
Multi-State Value