User's Manual
Design
Siemens PLT 130
.
1994
3/6
Bus configurations
Bus configuration,
examples
Application Other conditions Cable connectors
20-m local bus Small plants
Max. 9 participants possible
Max. 20 m bus cable
Standard design redundant
Can only be used in instrumentation
rooms.
The guidelines for earthing and screen-
ing must be observed for the partici-
pants on the local bus.
Ensure i n particular that the partici-
pants have the same ground potential
(equipotential bonding, 0-V island).
Exceptions are valid for isolated l ocal
bus interface modules N-AS and N-AT.
N1 to N2,
N2 to N3 etc.: 6DS8 201-8 . .
Front plug on N1: 6DS9 200-8AA
20-m l ocal bus/4-km remote
bus
Large plants
Max. 100 participants possible
Max. 4 km remote bus cable
Max. 32 bus converters UI can be
used, power distribution subrack can
be used for 2 bus converters UI.
The guidelines for earthing and screen-
ing must be observed for the partici-
pants on the local bus.
Ensure i n particular that the partici-
pants have the same ground potential
(equipotential bonding, 0-V island).
Exceptions are valid for isolated l ocal
bus interface modules N-AS and N-AT.
N1 to UI: 6DS8 205-8 . .
N1 to N2,
N2 to N3 etc.: 6DS8 201-8 . .
20-m l ocal bus/4-km remote
bus, redundant
Large plants
Max. 100 participants possible
Max. 4 km remote bus cable
Max. 32 bus converters UI can be
used, power distribution subrack can
be used for 2 bus converters UI.
The guidelines for earthing and screen-
ing must be observed for the partici-
pants on the local bus.
Ensure i n particular that the partici-
pants have the same ground potential
(equipotential bonding, 0-V island).
Exceptions are valid for isolated l ocal
bus interface modules N-AS and N-AT.
N1 to U/1 and UI2: 6DS8 204-8 . .
N1 to N2,
N2 to N3 etc.: 6DS8 201-8 . .
Individual participant on
4-km remote bus
Medium-sized plants
Individual participant on remote bus
(large distances between individual
participants)
Max. peripheral configuration of
connected AS systems
Max. 32 participants possible
Max. 4 km remote bus cable
Interface module(s) for 20-m local bus
and bus converter in same cabinet or
subrack.
Power distribution subrack can be
used for 2 bus converters UI per
cabinet.
N to UI: 6DS8 205-8 . .
Individual participant on
4-km remote bus, redundant
Medium-size plants
Individual participant on remote bus
(large distances between individual
participants)
Max. peripheral configuration of
connected AS systems
Max. 32 participants possible
Max. 4 km remote bus cable
Interface module(s) for 20-m local bus
and bus converter in same cabinet or
subrack.
Power distribution subrack can be
used for 2 bus converters UI per
cabinet.
N to UI1 and UI2: 6DS8 204-8 . .
AF Connector board ”Remote bus” N Interface module for 20-m local bus
FB Remote bus UI Inductive bus converter