Configuration examples
G
Vöovl jtrr
Cerloop
GW-20.xx
NET Pad
MK7022
GW-21
GW-21
CCTV CS-4 W-422CMXCS-4CCTV CC-30 CS-11 CC-60 CS-4
GW-21
Technical Data
Supported Protocols
- CDDL/CMSDL for LMS/CMS systems
- Cerban (CZ10/12, CC4 via CK4, CC11 via CK11, CC60)
- Cerban (STT-10, STT-11 via STK-11)
- ISO 1745 MK-7022 / Cerloop
- CerTalk (CC30 Cerpass)
- SIZE (Transliner)
- CMX-DL (CMX - CF-9003 I/O devices)
- CCTV Comerson (CDDL/CDSF)
- SEEP (Westinghouse SExxx)
- 8x00 Allegiant - Burle CCTV
- CDDL/CDSF for Siemens Simatrix CCTV
- CDDL/CDSF for Comerson CCTV MX series
- CDDL/CDSF Subsystem PAD (for foreign subsystem)
up to 9600 baud
300 or 600 baud
300 baud
1200 or 2400 baud
9600 baud
9600 baud
up to 9600 baud (4800 suggested)
9600 baud
up to 9600 baud
1200 baud
9600 baud
9600 baud
up to 9600 baud
Connectors
Configuration
on Back-plane: terminals for all six comm.
Lines Jumpers and Flash EPROM
GW-21
Power supply requirements
External DC power supply
Input voltage
Maximum current absorption
from 10 to 30 V DC
250 mA
PS-21
optional Power supply unit
Requirements
Output
External AC power supply
Input voltage
Maximum current absorption
Output voltage
Current
100-240 V AC, 50/60 Hz
2 A
13.8 V DC
4 A
Operating conditions
Temperature range
Humidity
0 to 50 °C
10 to 95 % non condensing
Dimensions
GW-21
BOX-21
130 (H) x 80 (D) x 175 (W) mm
200 (H) x 200 (D) x 300 (W ) mm
Weight
GW-21
BOX-21, including GW-21 and PS-21
500 gr
9 kg