User Manual

Siemens Building Technologies
Cerberus Division
CH-8708 Männedorf
Alte Landstrasse 411
Tel. +41 1-922 61 11
Fax +41 1-922 64 50
www.cerberus.ch
Cerberus
Security
for People
and Assets
Siemens Building Technologies
Cerberus Division
Replaces - Doc.no E1140
Edition: 06.2000
In a typical configuration, the CBS-3 is connected to a CZxx control panel downward. Upward, the two connection
lines can be used to send messages and receive commands to and from an LMS and any other supervising
system.
GW-0x
CBS-3
CZxx
Cerban line
Any user
provided device
Cerban line
Cerban line
Line slitter
Subsystem
Technical Data
Communications
Protocols supported and baud rate
Communication line 1
Communication line 2
Communication line 3
Cable (RS 232 signal)
Cable (power supply)
Max. distance
Cerban slave 300 bauds
Cerban master 300 bauds
Cerban master 300 bauds
shielded cable, with twisted pairs (minimum section 0.50
mm2)
the section must be computed according to the distance, in
order to get a voltage on the device compliant with technical
data
between the CBS-3 and the connected devices 1000 m
Power supply requirements
Input voltage
Max. current absorption
10-30 V
500 mA
Operating conditions
Temperature range
Humidity
15 to 50 °C
10 to 90 % non condensing
Dimensions
including metal bracket 150 (W) x 172 (D) x 36 (H) mm
Weight
including metal bracket 520 g