ANNEX B - Subsystems messages
18[34]
Data and design subject to change without notice. Supply subject to availability
© Copyright by CERBERUS AG, CH-8708 Männedorf, Switzerland 1995
02.99 e1754.doc
8.1 Initiating messages
8.1.1 CERBAN CZ10
Description Message (in hexadecimal)
LOCAL ALARM [short] 01 gg
GENERAL ALARM [short] 02 gg
ACKNOWLEDGED ALARM [short] 03 gg
RESET ALARM [short] 04 gg
DIGITAL INPUT OFF [short] 05 gg
DIGITAL INPUT ON [short] 06 gg
DIGITAL INPUT FAULT [short] 07 gg
DIGITAL INPUT CALL [short] 08 gg
NORMAL GROUP [short] 09 gg
EXCLUDED GROUP [short] 0A gg
FAULT GROUP [short] 0B gg
DETECTOR FAULT GROUP [short] 0C gg
TEST GROUP [short] 0D gg
ALARM TEST GROUP [short] 0E gg
ORGANISATION NIGHT FF 0L LL FF 00 55 60
ORGANISATION DAY FF 0L LL FF 00 55 61
FAULT (ANY) FF 0L LL FF 00 3A 3A
END OF FAULT (ANY) FF 0L LL FF 00 3A 3B
CONTROL FAULT 5A 0L LL 00 00 3A 3A
END OF CONTROL FAULT 5A 0L LL 00 00 3A 3B
POWER SUPPLY FAULT 5A 0L LL 00 00 3C 46
BATTERY OPERATIONS 5A 0L LL 00 00 3C 3D
END OF POWER FAULT/BATTERY OPERATION 5A 0L LL 00 00 3C 3C
GROUP .. ON FF 0L LL FF gg 64 3C
GROUP .. OFF FF 0L LL FF gg 64 56
GROUP ..TEST FF 0L LL FF gg 64 57
GROUP .. FAULT FF 0L LL FF gg 64 46
FIRE ALARM - GROUP .. (DETECTORS) 57 0L LL A1 gg FF 01
FIRE ALARM - GROUP .. (PUSHBUTTONS) 57 0L LL A1 gg FF 02
FIRE ALARM - ANY GROUP (DETECTORS) 57 0L LL A1 FF FF 01
FIRE ALARM - ANY GROUP (PUSHBUTTONS) 57 0L LL A1 FF FF 02
FIRE ALARM ACKNOWLEDGMENT 57 0L LL A1 00 00 82
FIRE ALARM RESET 57 0L LL A1 00 00 85
FIRE ORGANISATION NIGHT 57 0L LL A1 00 55 60
FIRE ORGANISATION DAY 57 0L LL A1 00 55 61
PART OF FIRE SECTOR OFF 57 0L LL A1 00 63 3A
END PART OF FIRE SECTOR OFF 57 0L LL A1 00 63 3B
FIRE FAULT 57 0L LL A1 00 3A 3A
END OF FIRE FAULT 57 0L LL A1 00 3A 3B
PLANT ALARM - GROUP .. (DETECTORS) 50 0L LL E2 gg FF 01
PLANT ALARM - GROUP .. (PUSHBUTTONS) 50 0L LL E2 gg FF 02
PLANT ALARM - ANY GROUP ..(DETECTORS) 50 0L LL E2 FF FF 01
PLANT ALARM - ANY GROUP (PUSHBUTTONS) 50 0L LL E2 FF FF 02
PLANT ALARM ACKNOWLEDGEMENT 50 0L LL E2 00 00 82
PLANT ALARM RESET 50 0L LL E2 00 00 85
PLANT ORGANISATION NIGHT 50 0L LL E2 00 55 60
PLANT ORGANISATION DAY 50 0L LL E2 00 55 61
PART OF PLANT SECTOR OFF 50 0L LL E2 00 63 3A
END PART OF PLANT SECTOR OFF 50 0L LL E2 00 63 3B
PLANT FAULT 50 0L LL E2 00 3A 3A
END OF PLANT FAULT 50 0L LL E2 00 3A 3B