ANNEX B - Subsystems messages
20[34]
Data and design subject to change without notice. Supply subject to availability
© Copyright by CERBERUS AG, CH-8708 Männedorf, Switzerland 1995
02.99 e1754.doc
Description Message (in hexadecimal)
PANEL PROTECTION ON 53 4L LL 00 D4 58 55
PANEL PROTECTION OFF 53 4L LL 00 D4 58 56
PANEL PROTECTION ERRONEOUSLY OFF 53 2L LL 00 D4 58 66
CODE ALARM 53 2L LL 00 D3 FF 55
CODE ALARM ACK 53 3L LL 00 D3 FF 55
CODE ALARM RESET 53 4L LL 00 D3 FF 85
DETECTOR ADDRESS ... NORMAL 53 4L LL gg ee 69 3C
DETECTOR ADDRESS ... OUT 53 4L LL gg ee 69 5E
DETECTOR ADDRESS .. TEST 53 4L LL gg ee 69 57
DETECTOR ADDRESS .. NOT READY 53 2L LL gg ee 69 5F
DETECTOR ADDRESS ..ERRONEOUSLY OFF 53 2L LL gg ee 69 66
DETECTOR ADDRESS .. TEST ALARM 53 4L LL gg ee 69 0B
CONTROL DEVICE .. ACTIVE 53 4L LL ED ee 68 4F
CONTROL DEVICE .. INACTIVE 53 4L LL ED ee 68 4D
PART OF INTRUSION SECTOR OFF 53 2L LL 00 EC 75 3A
END PART OF INTRUSION SECTOR OFF 53 4L LL 00 EC 75 3B
TIME PROGRAM ON 53 4L LL EB 0t 6B 55
TIME PROGRAM OFF 53 4L LL EB 0t 6B 56
TIME PROGRAM FORCED ON 53 4L LL EB 0t 6B 70
TIME PROGRAM FORCED OFF 53 4L LL EB 0t 6B 71
OPERATOR'S LOGIN 53 4L LL EE LL 70 6B
OPERATOR'S LOGOUT 53 4L LL EE LL 70 6C
DIGITAL INPUT .. ON 50 0L LL E1 0i 41 4F
DIGITAL INPUT .. OFF 50 0L LL E1 0i 41 3C
LLL=local address
t=program
gg=group
ee=element
i=input