FC18 Controller Operating manual A5Q00037963 Smart Infrastructure
Operating Manual of FC18 Controller TABLE OF CONTENTS CHAPTER 1 SYSTEM OVERVIEW ················································································································ 3 1. 2. 3. 4. 5.
Operating Manual of FC18 Controller APPENDIX 2 OPERABLE ITEM LIST············································································································ 61 APPENDIX 3 EQUIPMENT GROUPING TABLE································································································· 63 APPENDIX 4 RULES FOR LOGIC EXPRESSION ······························································································ 64 APPENDIX 5 INPUT METHOD ·······································
Operating Manual of FC18 Controller CHAPTER 1 SYSTEM OVERVIEW There are three types of FC18 series controllers: - FC1820 fire alarm controller (interlocking) FC1840 fire alarm controller (interlocking) FC1840C fire alarm controller (no interlocking panel, no printer) 1. FEATURES - FC1820 and FC1840 fulfill Chinese Standard of GB4717-2005 and GB16806-2006. FC1840C fulfill Chinese Standard of GB4717-2005. Multi-language operation menu designed with windows style for fast and easy operation.
Operating Manual of FC18 Controller 2. TECHNICAL DATA Item No. of line modules No. of points LCD screen Parameter FC1820 FC1840 FC1840C 1 2 2 252 504 504 320×240 pixels,backlit No. of programmable input/output on mainboard No. of zone of interlocking panel No. of NAC (0.5mA @24VDC) Max. history records 2 8 0 1 10000 Max. distance between controllers within FC18-BUS 1,000 m Max. No. of controllers connected within FC18-BUS 32 Max.
Operating Manual of FC18 Controller 3. DIMENSIONS Fig. 1-1 FC18 Appearance Fig. 1-2 FC18 Dimensions (mm) 4. COMPATIBLE LIST No. Type Description 1. FDT181 Addressable heat detector 2. FDO181 Addressable smoke detector 3. FDM181 Addressable manual call point 4. FDCI181-2 Addressable input module 5. FDCIO181-2 Addressable input/output module 6. FDCI181-1 Addressable input module 7. FDCIO181-1 Addressable input/output module 8. FT1810 Addressable floor repeater display 9.
Operating Manual of FC18 Controller 5. SYSTEM STRUCTURE - Up to 32 FC1820/40(C) controllers can be networked together. Any controller can be set as master controller to supervise devices connected with its slave controller and its own. Fig.
Operating Manual of FC18 Controller Printer Keyboard 1 Terminal board Power supply Main board Line card 2 Line card 1 LED screen CPU board Battery Keyboard 2 Interlocking panel Fig.
Operating Manual of FC18 Controller CHAPTER 2 INSTALLATION 1. INSTALLATION Fig. 2-1 Dimensions (mm) Installation must comply with the local regulation! 1. Ensure the wall is dry, clean, flat and firm in which the controller is installed. 2. Chose a proper installation location to make sure the front door can be opened smoothly. 3. Mark the drillings for 4 installation holes on the wall. (Fig. 2-1) 4. Drill the holes, put expansion bolts in and insert the M6 screws. 5.
Operating Manual of FC18 Controller 2. CONNECTION DIAGRAM Fig. 2-2 Terminal line Note: In loop mode, wires from BP1 must end at AP1; wires from BS1 must end at AS1. The connection of field devices (except FDCL181 isolator) is polarity free. Fig. 2-3 Line card connection diagram (the same for Line 2) Fig. 2-4 FRT/Mimic driver connection diagram Note: Ensure positive and negative connections are properly in place; FC18-BUS is polarity sensitive. Connect a 120Ω resistor as monitoring resistor.
Operating Manual of FC18 Controller Fig. 2-7 Main board input/output connection diagram Fig. 2-8 Interlocking panel connection diagram (the same for other channels) Note: the load range of each output is 24VDC, 600Ω – 1.2kΩ 3. DIP-SWITCH Each controller/interlocking panel has an eight-digit Dip-switch for address setting. Each Dip-switch can set address 1-32 within its first 6 digits.
Operating Manual of FC18 Controller 4. Power Supply - Stable and reliable DC output - Auto switch between main power and battery - Alternative AC power switch - Charge and protect battery - Monitor main power, battery, trouble status - Auto recoverable current protection circuit for overload and short circuit Switch between 220VAC and 110VAC Fig.
Operating Manual of FC18 Controller Connect to port Connect to Connect to port “Pwr ” PS” on main unit battery Status” on main unit Connect external AC input Fig. 2-10 Wire connection Specification of power supply Input voltage 110/220 VAC Input frequency 60/50 Hz Output voltage 24 VDC Output current 5A AC fuse capacity 110VAC: 3.15A DC fuse capacity 5A Operating temperature 0 ~ +40℃ 220VAC:1.
Operating Manual of FC18 Controller CHAPTER 3 OPERATION 1. INTERFACE Fig. 3-1 Operation panel ① LCD The LCD backlight automatically turns off within the preset time in the idle mode; the preset time can be adjusted in the parameter setting. Press any key will turn on the LCD again. ② Printer There are two indicators and two buttons on the printer panel. Indicator: the green LED indicates power-up state while the red LED for operation state (on: online; off: offline).
Operating Manual of FC18 Controller ¹ System trouble: On when system hardware/software is faulty. ¹ Trouble: On when trouble occurs; off when trouble is resolved. ¹ Activation: On when some equipment (such as output module or main board output port) is activated; off when activation signal disappears and “reset” is pressed. ¹ Confirmation: On when controller receives confirmation signal; off when the signal disappears. ¹ NAC trouble: On when trouble occurs on NAC line; off when trouble disappears.
Operating Manual of FC18 Controller until master is reset. ⑤ Interlocking panel The interlocking panel has 8 output channels. Each channel has indicators to indicate trouble, activation and confirmation status. Each channel can be controlled manually with Activation/Deactivation button. Only level 2&3 user can access. Press the button to activate it and press it again to deactivate it, so on and so forth. ¹ Trouble: On when there is trouble; off when trouble is solved.
Operating Manual of FC18 Controller 2. LCD WINDOW ① ② ③ Fig. 3-2 Display screen FC18 controller has 3 windows which are menu window (1), browser window (2) and statistics window (3). ① Menu window: ¹ Display different operation menus according to different user levels. Items for Level 3 are shown as follows.
Operating Manual of FC18 Controller ② Browser window: ¹ Display real-time events: fire alarm, activation & confirmation, trouble, supervision, disable, test and walk-test. ¹ Display node tree. ¹ Priority of display: fire alarm→ activation & confirmation→ supervision→ disable→ trouble→ test/walk-test→ normal. ③ Statistics window: ¹ Display total number of real-time events including fire alarm, activation, confirmation, trouble, supervision and disable.
Operating Manual of FC18 Controller 3. USER LEVEL l FC18 has 3 user levels. User level is displayed at the lower right corner of the screen (Fig. 3-2) l Users of different levels have their own matching privileges and interfaces.
Operating Manual of FC18 Controller 3.1 1. Login Press “Menu” to browse the main menu. Display main menu. 2. Press”→” to select “Login”, and then press “OK”. Password entry window pops out. Fig. 3-3 3. Enter the password for Level2/3 and press “OK”. Login as a Level 2/3 user if the password entered is correct. (Press “←” to delete previous input.) Note: Default password for Level 2 is 1234, for Level 3 is 4321. Default password can be changed by FXS1800 software tool.
Operating Manual of FC18 Controller 4. STATUS TYPES FC18 controller contains 8 status types: normal, fire alarm/activation, trouble, supervision, disable, test/walk-test and locate. Normal: l Main power supply indicator on l Auto/Manual indicator on l No events taken place such as fire alarm/activation, trouble, supervision, Event Help Login System Normal SIEMENS Building SIEMENS disable, test, walk-test etc.
Operating Manual of FC18 Controller Activation status: l Activation indicator on (flashing when there is no confirmation) l LCD shown as the figure l Acknowledge/Silence indicator flashing l Buzzer ringing Activation 0001 Activation Output 1 / 01.005.008 2008-08-08 10:10:13 Fig. 4-5 Confirmation status: l Confirmation indicator on l LCD shown as the figure l Acknowledge/Silence indicator flashing l Buzzer ringing Confirmation 0001 Confirmation Output 1 / 01.005.
Operating Manual of FC18 Controller 5. FIRE ALARM EVENT HANDLING Fire alarm status: l Fire alarm indicator turns on l Fire event with customer information shown in the LCD as the figure l Acknowledge/Silence indicator flashing l NAC activation indicator turns on l Buzzer turns on l NAC devices activated How to handle: 1. Press Acknowledge/Silence to silence the buzzer: l Fig. 5-1fire alarm interface Under Level 1 interface, a login interface pops out automatically.
Operating Manual of FC18 Controller 6. TROUBLE EVENT HANDLING Trouble status: l Trouble indicator turns on l Trouble events are shown on the LCD as the figure l Acknowledge/Silence indicator flashing l Buzzer turns on How to handle: 1. Press “Acknowledge/Silence” to silence the buzzer: l Under Level 1 interface, a login interface pops out automatically. Enter Fig. 6-1 Level 2/3 password and press “OK” to return back to fire alarm window then press “Acknowledge/Silence”.
Operating Manual of FC18 Controller 7. SUPERVISION EVENT HANDLING Supervision status: l Supervision indicator on l Supervision events are shown on the LCD as the figure l Acknowledge/Silence indicator flashing l Buzzer turns on How to handle: 1. Press “Acknowledge/Silence” to silence the buzzer: l Under Level 1 interface, a login interface pops out automatically. Enter Fig.7-1 Level 2/3 password and press “OK” to return back to fire alarm window then press “Acknowledge/Silence”.
Operating Manual of FC18 Controller 8. ACTIVATION/CONFIRMATION EVENT HANDLING Activation status: l Activation indicator on (flashing if there is no confirmation) l Confirmation indicator on (only if there is confirmation signal) l Activation events are shown on the LCD as the figure l Acknowledge/Silence indicator flashing l Buzzer turns on How to handle: 1. Press Acknowledge/Silence to silence the buzzer: l Under Level 1 interface, a login interface pops out automatically. Enter Fig.
Operating Manual of FC18 Controller 9. REAL-TIME QUERY FC18 fire alarm controller (interlocking) contains ten types of real-time events: Table 3-2 Types of real-time events Priority Fire alarm/activation 1 Supervision 2 Disable 3 Trouble 4 Test 5 Walk-test 5 Locate 5 Unconfigure equipment 6 Unknown equipment 7 Inconsistent equipment 8 Exchange equipment 9 Unconfigure equipment: Equipments not on the engineering document list. Unknown equipment: Equipments not listed by Table 1-2.
Operating Manual of FC18 Controller 10. HOW TO QUERY EQUIPMENT PROPERTY Steps: 1. Select a station, a line or a point and press “→” to pop out a shortcut menu (Fig. 10-1), then select “Property” and press “OK” to pop out a property window. (Fig. 10-2) Trouble 0002 COMM trouble 2008-08-08 10:10:10 Interlocking Line / 01.005 0001 Other Property 2008-08-08 10:10:08 Room 1008, BuildingHistory 1 / 01.001.291 Fig.10-1 Property 2. Press “C” to quit equipment property query.
Operating Manual of FC18 Controller 11. HOW TO QUERY HISTORY FC18 fire alarm controller (interlocking) contains 11 types of history records which are fire alarm, trouble, supervision, activation/confirmation, disable, test and walk-test, unconfigure equipment, unknown equipment, inconsistent equipment, exchange equipment. The first six types support advanced query. Steps: 1. Select a station, a line or a point and press “→” to pop out a shortcut menu, and then press “↓” to “History” (Fig. 11-1).
Operating Manual of FC18 Controller 12. HOW TO DISABLE/ENABLE Function: The controller should be disabled when the house is being decorated or there are equipment damages or failure. It should be resumed to normal state as soon as the decorating work or equipment repair is finished. Note: Disabled equipment cannot send any message to controller. Equipment cannot be disabled when being replaced. Steps to disable: 1. Press “Menu” to browse the main menu (Fig.12-1). Fig.12-1 Main menu displayed. 2.
Operating Manual of FC18 Controller 13. HOW TO ACTIVATE/DEACTIVATE THE CONTROLLER Function: Through controller, manually activation/deactivation mainboard output, output module, interlocking panel output and NAC devices etc. Steps to activation: 1. Press “Menu” to browse the main menu (Fig. 13-1). Main menu displayed. Fig.13-1 2. Press “→” to select “Brow” submenu (Fig. 13-2). Press “↓” to select “All”, then press “OK” to display the tree diagram (Fig. 13-3).
Operating Manual of FC18 Controller 14. HOW TO TEST/WALK-TEST Function: To test whether the alarm device is in normal status. Under test/walk-test mode, an alarm will be triggered when there is an alarm event while the interlocking equipment will not be activated. Make sure the controller is back to normal after the test. Difference between test and walk-test: Test: Fire alarms cannot reset automatically under test mode. Controller need to be resumed back to normal status by manual reset.
Operating Manual of FC18 Controller 15. HOW TO LOCATE/STOP LOCATING Function: To locate equipment. Steps to locate: 1. Press “Menu” to browse the main menu (Fig. 15-1) Main menu displayed. 2. Press “→” to select “Brow” submenu (Fig. 15-2). Press “↓” to select “All”, then press “OK” to display the tree diagram (Fig. 15-3). Search down level by level through stations, lines and points until you find the equipment you Fig.15-1 are looking for. 3. Press “→” to pop out the shortcut menu (Fig.15-4).
Operating Manual of FC18 Controller 16. HOW TO ADJUST BUZZER LEVEL Function: Turn up or down the buzzer between level 0-7. Level 0 is mute mode. Steps: 1. Press “Menu” to browse the main menu (Fig. 16-1) Main menu displayed. Fig.16-1 2. Press “→” to select “Brow” submenu (Fig. 16-2). Select "All" and then press “OK”. Now the tree diagram will be displayed in the window (Fig.16-3). 3. Use "↓" / "↑" to select the controller you are looking for. 4. Press “→” to pop out the shortcut menu (Fig.16-4).
Operating Manual of FC18 Controller 17. HOW TO SET LOGIN TIME Function: Under 2/3 level, if there is no operation in preset login time, controller will automatically log out to 1level. Setting range: 1-60 minutes. Steps: 1. Press “Menu” to browse the main menu (Fig. 17-1) Main menu displayed. Fig.17-1 2. Press “→” to select “Browse” submenu (Fig. 17-2). Select "All" and then press “OK”. Now the tree diagram will be displayed in the window (Fig.17-3). Fig.17-2 3.
Operating Manual of FC18 Controller 18. HOW TO SET WALK-TEST TIME Function: Controller being tested will restore to normal status automatically after the preset walk-test time. Setting range: 1-60 min. Steps: 1. Press “Menu” to browse the main menu (Fig. 18-1) Main menu displayed. Fig.18-1 2. Press “→” to select “Brow” submenu (Fig. 18-2). Select "All" and then press “OK”. Now the tree diagram will be displayed in the window (Fig.17-3). 3. Use "↓" / "↑" to select the controller you are looking for.
Operating Manual of FC18 Controller 19. HOW TO SET LCD CLOSING TIME Function: LCD turns off its back light if there is no operation or event during the preset LCD closing time. Press any key to turn on the back light. Setting range: 1-60 min. Steps: 1. Press “Menu” to browse the main menu (Fig. 19-1) Main menu displayed. Fig.19-1 2. Press “→” to select “Browse” submenu (Fig. 19-2). Select "All" and then press “OK”. Now the tree diagram will be displayed in the window (Fig.19-3). Fig.19-2 3.
Operating Manual of FC18 Controller 20. HOW TO SET TIME Function: To set system time. Steps: 1. Press “Menu” to browse the main menu (Fig. 20-1) Main menu displayed. Fig.20-1 2. Press “→” to pop out the "Tool" submenu (Fig.20-2). Select “Set Time" and press “OK” to enter the time setting interface (Fig.20-3). 3. Press "←" to delete the previous number and enter the exact time and date then press "OK". The change will take effect immediately. Fig.
Operating Manual of FC18 Controller 21. HOW TO CHECK SYSTEM Function: To check whether the LCD, indicators, printer and the buzzer are in normal state. Steps: 1. Press “Menu” to browse the main menu (Fig. 21-1) Main menu displayed. Fig.21-1 2. Press “→” to pop out the "Tool" submenu (Fig.21-2). Press "↓" to select “Check System" and press “OK” to display the checking system window (Fig.21-3). Press "OK" to examine the system. - LCD: Flash in white and black once for each.
Operating Manual of FC18 Controller 22. HOW TO SAVE CONFIGURE Function: Save changes permanently, otherwise the changes will be lost when the system is restarted. Steps: 1. Press “Menu” to browse the main menu (Fig. 22-1) Main menu displayed. Fig.22-1 2. Press “→” to pop out the "Conf" submenu (Fig.22-2). Press "↓" to select “Save Configure" and press “OK” to display the configuration saving window (Fig.22-3). Press "OK" to save the changes. Fig.22-2 3.
Operating Manual of FC18 Controller 23. HOW TO EDIT PARAMETER Function: To modify parameters in system. See Appendix table 1 for details. Steps: 1. Press “Menu” to browse the main menu (Fig. 23-1) Main menu displayed. Fig.23-1 2. Press “→” to select “Brow” submenu (Fig. 23-2). Press “↓” to select the item which contains the equipment whose parameters need to be modified, and then press “OK”. Now the equipment will be displayed directly in the window.
Operating Manual of FC18 Controller 24. HOW TO CREATE/VIEW LOGIC Function: To create/view logic among detection group, supervision group and control output group. Steps: 1. Press “Menu” to browse the main menu (Fig. 24-1) Main menu displayed. 2. Press “→” to select “Brow” submenu (Fig. 24-2). Select "All" and then press “OK”. Now the tree diagram will be displayed in the window (Fig.24-3). Fig.24-1 Press “↓”/” ↑” to find out the group for which you want to build an interlock. 3.
Operating Manual of FC18 Controller 25. HOW TO EDIT/DELETE LOGIC Function: To modify or delete logic. Steps: 1. Press “Menu” to browse the main menu (Fig. 25-1) Main menu displayed. 2. Press “→” to select “Browse” submenu (Fig. 25-2). Select "All" and then Fig.25-1 press “OK”. Now the tree diagram will be displayed in the window (Fig.25-3). Press “↓”/“↑” to find out the expression to be modified. 3. Press “→” to pop out the shortcut menu (Fig.25-3).
Operating Manual of FC18 Controller 26. HOW TO ASSIGN GROUP/ FRT Function: It's more convenient to edit logic with the concept of "Group". There are four groups in the system: detection group, control output group, supervision group and FRT group. See Appendix table 3 for details. Steps: 1. Press “Menu” to browse the main menu (Fig. 26-1) Main menu displayed. 2. Press “→” to select “Brow” submenu (Fig. 26-2). Select "All" and then press Fig.26-1 “OK”.
Operating Manual of FC18 Controller 27. HOW TO GET HELP Function: To show the company name, system edition, product series No, download time of configuration file and modification time. Steps: 1. Press “Menu” to browse the main menu (Fig. 27-1) Main menu displayed. Fig.27-1 2. Press “→” to select “Help” submenu (Fig. 27-2). Press "OK" to display the help information window (Fig.27-3). Fig.27-2 3. Press "C" to return to the original window. Fig.
Operating Manual of FC18 Controller 28. HOW TO OPERATE INTERLOCKING PANEL Function: The interlocking penal has 8 channels of input/output. Each of them has indicators of trouble, activation and confirmation to indicate its state, as well as activation/deactivation key for manual control. Steps: ¹ When the controller is in automatic status, the controller can activate spot equipment through logical relation. The "activation" indicator is on when activation order is given.
Operating Manual of FC18 Controller 29. HOW TO OPEN/CLOSE A PRINTER Function: When the printer is open, it can print real-time events at any time and print history records if needed (see "History Query"); when it is off, it cannot print anything. Steps to open printer: 1. Press “Menu” to browse the main menu (Fig. 29-1) Main menu displayed. Fig.29-1 2. Press “→” to select “Brow” submenu (Fig. 29-2). Select "All" and then press “OK”. Now the tree diagram will be displayed in the window (Fig.29-3).
Operating Manual of FC18 Controller Operations of printer: There are two indicators and two keys. Indicators are under the transparent key. Indicator: Green indicator indicates electrifying state of printer; red indicator indicates working state of printer (online/offline). Green On Normal power supply indicator Off No power supply On Online Off Offline Red indicator Fig.29-6 Keys: SEL: Choose online/offline states of printer; LF: Line feed.
Operating Manual of FC18 Controller 30. HOW TO REPLACE DEVICE Function: To copy the configuration information to the new equipment when the old one is replaced. Steps: 1. Press “Menu” to browse the main menu (Fig. 30-1) Main menu displayed. Fig.30-1 2. Press “→” to select “Browse” submenu (Fig. 30-2). Press "↓" to select " Unconfigure" and then press “OK”. Now the equipments unconfigure will be displayed in the window (Fig.30-3). Fig.30-2 3. Press "↓" to select equipment to configure.
Operating Manual of FC18 Controller 31. HOW TO UPGRADE TO FC1840 Function: The FC18 wall-mounted controller has two types: the FC1820 and the FC1840. FC1820 can be upgraded to FC 1840 through adding a loop card and conducting the following operations. Event Steps: 1. Press “Menu” to browse the main menu (Fig. 31-1) Main menu displayed.
Operating Manual of FC18 Controller 32. HOW TO CHANGE LANGUAGE Function: The system provides four kinds of language: English, Taiwan, Hongkong, and Portuguese. Apply languages as needed. Steps: 1. Press “Menu” to browse the main menu (Fig. 32-1). Main menu displayed. 2. Press “→” to select “Lang” submenu (Fig. 32-2). Select a language you need and press “OK”. 3. Fig.32-1 The system language is changed. Note: Fig.32-2 The saved change will take effect immediately.
Operating Manual of FC18 Controller 33. HOW TO QUERY THE INFORMATION OF OTHER EVENTS Function: Other events include: Test, Walktest, Locate, Unconfigure, Unknown, Inconsistent, and Exchage. Through this function, can check the qty for each event. Step: 1. Press “Menu” to browse the main menu (Fig. 33-1). Main menu displayed. Fig. 33-1 2. Press “→” to select “Brow” submenu (Fig. 33-2). Press “↓” to select “Other”, and then press “OK” to display the information (Fig. 33-3). 3.
Operating Manual of FC18 Controller 34. HOW TO EXTEND PRINTER PORT Function: when the communication port on the main board is occupied by the FMS8000 graphic display device, the debugging port on the CPU board can be configured as the printer port via this operation。 Steps: 1. Press “Menu” to browse the main menu (Fig. 34-1). Main menu displayed. Fig. 34-1 2. Press “→” to pop out the "Tool" submenu (Fig.34-2). Select “->Printer" and press “OK”, then this port is configured as a printer port.
Operating Manual of FC18 Controller 35. HOW TO SYNCHRONIZE CONFIGURATION Function: After the configuration file of the master controller in FS18 automatic fire alarm system is updated, the configuration file is issued through FC18-Bus and the configuration file of each slave controller is updated accordingly. Steps: 1. Press “Menu” to browse the main menu (Fig. 35-1) Main menu displayed.
Operating Manual of FC18 Controller 36. HOW TO COLLECT CONFIGURATION AND SYNCHRONIZE Function: After the configuration file of the slave controllers in FS18 automatic fire alarm system is updated, the master controller collects the updated configuration file of the slaves via FC18-Bus and synchronizes them to each related slave. Steps: 1. Press “Menu” to browse the main menu (Fig. 36-1) Main menu displayed.
Operating Manual of FC18 Controller 37. HOW TO CHECK THE SUMMARY OF CONTROLLER AUTO/MANUAL STATUS Function: The FC18 fire alarm controller can check the summary of auto or manual status for each controller in the network via this operation. Steps: 1. Press “Menu” to browse the main menu (Fig. 37-1) Main menu displayed. 2. Press “→” to select “Brow” submenu (Fig. 37-2). Press "↓" to select "Auto-Manual" and then press “OK”. The summary of controller’s Fig.37-1 auto/manual status window displays. 3.
Operating Manual of FC18 Controller CHAPTER 4 MAINTENANCE 1. DAILY EXAMINATION Operator on duty should examine controllers every day and record status. If there is fire alarm, error or other abnormal status, please follow “Emergency Failure Guideline”; when controller gets normal again, the event should be recorded. 2. EMERGENCY AND TROUBLE HANDLING Table 4-1 No. 1. Failure phenomenon Failure or damage of function keys, LED, LCD, etc. 2. No voltage indication of controller 3.
Operating Manual of FC18 Controller No.
Operating Manual of FC18 Controller APPENDIX 1 PARAMETER LIST Equipment type Editable item Parameter description System Text System name Station Text Controller name Login time Under 2nd/3rd level, if there is no operation in preset login time, controller - FC1820 will automatically log out to 1st level. Effective value: 1-60 minutes.
Operating Manual of FC18 Controller Fire alarm input Text Equipment location/function description Text Equipment location/function description Inversion Option 1: Normal (Active When NO is closed) (default) (interlocking panel and main board input) Output without confirmation (FDCIO181) Option 2: Inverting (Active when NC is open) Signal Shape Option 1: Static (After activating, the output remains permanently active) (default) Option 2: Pulse (After activating, the output remains active for a certa
Operating Manual of FC18 Controller Output style Option 1: Switched voltage control output. (Default) Option 2: Dry contact Output with confirmation Text Equipment location description (interlocking panel and main Supervision time In preset supervision time, if there is no confirmation signal received, board output) system defines it as activation without confirmation. Default value is 10 seconds. Effective value: 1-600 seconds.
Operating Manual of FC18 Controller APPENDIX 2 OPERABLE ITEM LIST Controller: Operational item Controller Auto/Manual* Set time System Check FC1820 √ √ √ FC1840 √ √ √ [ * ] Auto/Manual can only be switched through buttons on controllers.
Operating Manual of FC18 Controller Group: Group Operational item Activation/ Disable/ Deactivation Enable √ ------- Detection group ------- ------- Supervision group ------- -------- FRT group ------- √ Control group “Ö“ indicates operational; “----” indicates not operational.
Operating Manual of FC18 Controller APPENDIX 3 EQUIPMENT GROUPING TABLE Equipment type Detecting group Control output Supervision Fire display group panel group group FDO181 Smoke detector √ √ FDT181 Heat detector √ √ FDM181 Manual Call Point √ √ FDHM181 Hydrant Manual Call Point √ √ FDCI181 Input module √ FDCIO181 Input/output module √ Main board supervision input √ Main board confirmation input Main board alarm input √ √ √ Main board output, interlocking panel output (withou
Operating Manual of FC18 Controller APPENDIX 4 RULES FOR LOGIC EXPRESSION 1. Logic expression: 01.0001.07+01.0002.07+01.0003.07=01.0004.10 1 2 Input 2. Output ① Group No.: xx.xxxx first two numbers express controller No.; last four numbers express group code.
Operating Manual of FC18 Controller ● “@N”: Union alarm in a group, 2≤N≤ total device amount; Example: 01.0001@2=01.0004; indicates that any 2 devices in group 01.0001 alarm can activate group 01.0004. Remark: when adding /deleting device in a group, the logic expression needs to be verified. ●When a logic expression need to activate more groups (output) simultaneously, use “,” to separate; Example: (01.0001+01.0002)*01.0003=01.0004, 01.0005; indicates that any group of 01.0001, 01.0002 and 01.
Operating Manual of FC18 Controller APPENDIX 5 INPUT METHOD Letter/Number input: 1. Press down letter/number key, then input content will switch between number and letter. 2. When switched to needed content, relieve the key to complete the input of needed letter/number. Special character input: 1. Press down number key (1), then input content will switch among '1', '.', '+', '*', '=', ';', '~', '(', ')', '[', ']', '{', '}', '!', ':', ‘space’, '-'. 2.
Operating Manual of FC18 Controller APPENDIX 6 “STICKER METHOD”EASY FOR COMMISSIONING In FD18 system, there is an exclusive ID number on each spot component. Engineer debug staffs can tear it down when installing, and fix to the equipment position in engineering drawings, so that after installation of all components, engineer file configuration can be made. Detailed operations are as follows: 1. Open the package. 2. Tear down the machine-readable ID number. 3.
Issued by Beijing Siemens Cerberus Electronics Ltd. No.1, Fengzhi East Road, Xibeiwang Haidian District, 100094 BEIJING, China +86 10 64768806 www.siemens.com/buildingtechnologies © Beijing Siemens Cerberus Electronics Ltd., 2012 Technical specifications and availability subject to change without notice. Document no.