Operating Instructions

Operating Manual of FC18 Controller
A6V10322968_f_en_-- 49 | 6 7
31. HOW TO UPGRADE TO FC1840
Function: The FC18 wall-mounted controller has two types: the FC1820 and the
FC1840. FC1820 can be upgraded to FC 1840 through adding a loop card and
conducting the following operations.
Steps:
1. Press “Menu” to browse the main menu (Fig. 31-1)
Main menu displayed.
2. Press “ to select “Brow” submenu (Fig. 31-2). Select "All" and then press
“OK”. Now the tree diagram will be displayed in the window (Fig.31-3). Use
"" / "" to select the host machine.
3. Press “Menu” to browse the main menu then press “” to select “Oper”
submenu. Select "upgrade to FC1840" (Fig.31-3) then press "OK".
4. System pop out dialog window to ask user whether to upgrade or not
(Fig.31-4). Press "OK" to upgrade to FC1840 or press "C" to give up.
Note:
The saved change will not take effect until the system is reset.
This operation can only be applied to host machine.
This operation can only be applied to FC1820.
FC1840 cannot be degraded to FC1820. If it's needed, it should be
done through PC and downloading configuring files.
System Normal
SIEMENS Building
SIEMENS
<2008-08-08 08:08:08>
System Normal
Event Brow Oper Conf Tool Help Login
SIEMENS Building
Alarm & active
Trouble
Supervision
Disable
Test
Walk-Test
Alarm & active
Fig.31-1
Fig.31-2
Fig.31-3
Fig.31-4