User Manual
Mounting
/ Installation
Detector base seal RS720
5
22 | 38
Building Technologies
A6V10218037_n_en_
--
Fire Safety
2019
-
03
-
25
5.2 Detector base seal RS720
● Use the detector base seal RS720 to install point detectors in wet rooms.
Protection category: IP42.
● Compatible with detector base DB72x and sounder base DBS720.
● Only use for recess-mounted cable entry.
Installing the detector base seal
● NOTICE! Excessively large holes in the detector base seal will impair the
potential IP protection category! Do not cut or drill holes in the detector base
seal. Without using a tool, push the lines through the detector base seal.
● Fit the detector base seal RS720 between the ceiling and the detector base
DB72x or the sounder base DBS720.