User Manual
Manual call points in C-NET
4.2 Manual call points FDM225/226 with direct operation
FDM225-RG
Manual call point with glass plate
Part no.
A5Q00013434
FDM225-RP
Manual call point with plastic element
Part no.
A5Q00012020
FDM226-RG
Manual call point with glass plate incl. housing
base
Part no.
A5Q00013435
FDM226-RP
Manual call point with plastic element incl.
housing base
Part no.
A5Q00013436
Documents
Product data sheet
009023
FDM225-RG, FDM225-RP
FDM226-RG, FDM226-RP
Technical description
009757
Application
For the immediate manual actuation of a fire alarm.
For indoor and outdoor application.
FDM225 for surface and recess mounting in easily accessible places.
FDM226 for surface mounting for IP67 applications
Addressable applicable.
Function
FDM225/226-RG
– Direct alarm actuation by pushing in the glass plate.
– By replacing the glass plate the push button is set back and the device is ready for operation again.
FDM225/226-RP
– Direct alarm actuation by pushing on the plastic element.
– The switch is set back with the key and the device is ready for operation again.
An additional protective cover FDMC295 protects the manual call point from unintentional glass break.
Technical data
Communication protocol
C-NET
Operating voltage
DC 13…33 V
Operating current (quiescent)
180 μA
Connection terminals
0.28…1.5 mm
2
Operating temperature
-25…+70 °C
Storage temperature
-30…+75 °C
Humidity
≤95 % rel.
Color
red, ~RAL 3000
Protection category EN 60529/IEC 60529
– FDM225
– FDM226
IP44
IP66
System compatibility C-NET
FS720
Standards
EN 54-11, EN 54-17
Dimensions
– FDM225
– FDM226
87 x 87 x 20 mm
87 x 87 (113) x 57 mm
Approvals
– FDM225-RG
– FDM225-RP
– FDM226-RG
– FDM226-RP
VdS G207092, LPCB 126ap/02
VdS G207092, LPCB 126ap/01
VdS G209194, LPCB 126ap/04
VdS G209194, LPCB 126ap/03
25
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc
CPS Fire Safety 04.2014