User Manual
Manual call points in C-NET
4.3 Manual call point FDM224 with direct operation
FDMH293-R
Housing red with glass and key
Part no.
A5Q00004023
FDMH293-Y
Housing yellow with glass and key
Part no.
A5Q00004908
FDMH293-B
Housing blue with glass and key
Part no.
A5Q00004909
FDMH293-G
Housing green with glass and key
Part no.
A5Q00004911
FDMH293-O
Housing orange with glass and key
Part no.
S54311-F2-A1
FDME224
Switching unit
Part no.
A5Q00009392
Documents
Product data sheet
007001
Technical description
007002
Application
For the immediate manual actuation of an alarm.
For indoor and outdoor application, equally suited for wet, humid and dusty areas.
For surface- and recess-mounted feed lines in easily accessible places.
Addressable applicable.
Function
Direct alarm actuation by smashing in the glass plate.
To replace the glass plate, open the housing door with the key, upon closing the door the button is reset.
Technical data
Communication protocol
C-NET
Operating voltage
DC 12…33 V
Operating current (quiescent)
200 μA
Ext. alarm indicator
2
Connection terminals
0.28…1.5 mm
2
Operating temperature
-25…+70 °C
Storage temperature
-30…+75 °C
Humidity
≤95 % rel.
Color
red, ~RAL 3000,
yellow, ~RAL 1023,
blue, ~RAL 5005,
green, ~RAL 6024,
orange, ~RAL 2011
Protection category EN 60529/IEC 60529
– with seal DMZ1197-AD
IP44
IP64
System compatibility C-NET
FS720
Standards
EN 54-11, EN 54-17
Dimensions
134,3 x 134,3 x 43,2 mm
Approvals
VdS G206123, LPCB 531k/10
28
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc
CPS Fire Safety 04.2014