User Manual
Line separator, Input/output modules in C-NET
FDCIO223
Transponder
Part no.
S24218-B102-A1
Documents
Product data sheet
009168
FDCIO223
2 Transzorb diode 20 V
2 x 560 Ω 1 %; 0.25 W
2 x 680 Ω 5 %; 0.25 W
2 x 2,7 kΩ 1 %; 0.35 W
2 x 3,3 kΩ 5 %; 0.25 W
2 Mounting feet
Technical description
009122
Application
For connection of collective fire detectors (GMT/conventional line, GMT/conventional line with shunt-
Zener-diode barrier (SB3) for explosion-hazard areas).
For monitored controls of e.g. smoke dampers, alarm devices, door mAgnets and extinguishing activa-
tion devices (adhere to country-specific instructions).
Monitored signal input for status and alarm messages or for acknowledging technical status.
Addressable applicable.
Function
The 2 inputs/outputs can be parameterized autonomously in each case as detector line collective, con-
tact input, control output, control output and input as acknowledgement with selectable monitoring time
frame.
Technical data
Operating voltage C-NET
DC 12…33 V
External power supply: Input voltage
DC 18…32 V
In-/outputs as collective detector line
GMT Siemens/Cerberus, Synova 300 or similar
Collective line factor (KLK) / end of line
32 / 20 V Transzorb diode
Control output
DC 24 V ±5 % / 2 A (fuse on site)
Contact input
End of line combinations
3,3 kΩ/680 Ω, 2,7 kΩ/560 Ω, 3,3 kΩ
Operating temperature
-25…+60 °C
Storage temperature
-30…+65 °C
Humidity
≤95 % rel.
Communication protocol
C-NET
Connection terminals
0.2…1.5 mm
2
(Auxiliary terminal 2.5 mm
2
)
Color housing / cover
white, ~RAL 9010 / transparent mAtt
Protection category EN 60529/IEC 60529
– with auxiliary housing FDCH221
IP30
IP65
System compatibility C-NET
FS720
Standards
CEA GEI I-084, EN 54-17, EN 54-18
Dimensions
132 x 90 x 24 mm
Approvals
VdS G206054, LPCB 531m/03
FDCIO224
Input/output module
Part no.
A5Q00018689
Documents
Product data sheet
007024
FDCIO224
8 Resistors
4 x 2k7; 1 %; 0.35 W
4 x 560 Ω; 1 %; 0.25 W
2 Mounting feet
Technical description
007023
Application
For the VdS interface for extinguishing activating devices.
Addressable applicable.
Function
4 inputs for potential-free contacts.
4 outputs with 4 potential-free relay contacts (AC 230 V / 4 A) for the VdS interface for extinguishing
controls.
Status indication by LED.
Technical data
Communication protocol
C-NET
Operating voltage
DC 12…33 V
Operating current
0,6…0,75 mA
Relay output (ohm)
AC 250 V, 4 A, max. 1000 VA
DC 30 V, 4 A, max. 120 W
Connection terminals
0.2…1.5 mm
2
(2.5 mm
2
)
Operating temperature
-25…+60 °C
Storage temperature
-30…+65 °C
Humidity
≤95 % rel.
Color housing / cover
white, ~RAL 9010 / transparent mAtt
Protection category EN 60529/IEC 60529
– with auxiliary housing FDCH221
IP30
IP65
System compatibility C-NET
FS720
Standards
CEA GEI I-084, EN 54-17, EN 54-18
Dimensions
130 x 90 x 20 mm
Approvals
VdS G207001
47
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc
CPS Fire Safety 04.2014