User Manual

Special detectors in C-NET
7.4 Aspirating smoke detectors
FDA221
Aspirating smoke detector (5S)
Part no.
S54333-F15-A1
FDA241
Aspirating smoke detector (8H)
Part no.
S54333-F17-A1
Document
Product data sheet
A6V10331032
FDA221
FDA241
Application
FDA221
The FDA221 series of detectors are a very early warning dual wavelength (blue & infra-red) smoke
detectors designed to protect small business-critical environments up to 500 m².
FDA241
The FDA221 series of detectors are a very early warning dual wavelength (blue & infra-red) smoke
detectors designed to protect small business-critical environments up to 800 m².
Function
The detector works by continually drawing air into sampling holes in a pipe net-work. The air is passed
into a uniquely designed detection chamber where light scattering technology detects the presence of
very small amounts of smoke. The FDA221and FDA241 detectors can communicate directly on the
FDnet/C-NET loops (with an optional FDCC221S PCB), so there is no need for separate relay or net-
work connections.
Technical data
Operating voltage
DC 19…30 V
Quiescent current
150 mA
Alarm current
250 mA
Display
4 Alarm state indicators(FDA241)
Purge, Dust (FDA241)
3 Alarm state indicators FDA221),
Fault and disabled indicators,
Smoke and airflow level bargraphs indicator
Area coverage
FDA221
FDA241
up to 500 m
2
up to 800 m
2
Alarm threshold
FDA221
FDA241
0.03 - 2.0 % obs/m / Info alarm, Pre-alarm, Fire 1 (5 sets)
2.0 - 20 % obs/m / Fire 2 (5 sets)
0.03 - 2.0 % obs/m / Info alarm, Pre-alarm, Fire 1 (10 sets)
2.0 - 20 % obs/m / Fire 2 (10 sets)
Air inlet pipe
Accepts both metric and American standard pipe sizes, External
diameter 25 mm, Internal diameter 21 mm
Pipe length
FDA221
FDA241
Single pipe length: 30m
Branched pipe length: 2 x 25m
Single pipe length: 60m
Branched pipe length: 2 x 60m
Relay output
3x 2 A / 30 V
Terminals
0.22.5 mm
2
(3012 AWG)
Dimensions (WxHxD)
155 x 280 x 114 mm
Operating temperature
-20+40 °C
Humidity
≤95 % rel. (no condensation)
Protection category
IP30
Approval
VdS, LPCB
7.4.1 Accessory
FDCC221S
Communication interface
Part no.
S24218-A201-A2
Application
For connecting the aspirating smoke detector FDA221 / FDA241 to FDnet/C-NET. The installation is not
permitted in the case of standalone operation. FDCC221S has its own ID. This ID is mAde visible to the
detector line and it replaces the ID of the aspirating smoke detector.