User Manual

Conventional and collective devices
8.3 Conventional / Collective 110-series detectors
OH110
Multi sensor fire detector (collective)
Part no.
S54372-F11-A1
Documents
Product data sheet
A6V10301051
Technical description
A6V10316298
Scope of delivery
Detector and dust cap
Application
For the detection of flaming fires caused by the combustion of liquid and solid mAtters, as well as smol-
dering fires and for reliable fire detection in environments with deceptive phenomena.
Function
Works according to the scattered light principle with one sensor, optical forward scattering.
Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke
particles. An additional heat sensor increases the fire detector’s immunity to deceptive phenomena.
Selectable detection behavior by two parameter sets: Parameter set 1 (Sensitive); Parameter set 2
(Robust)
Immunity against transient false alarm causes
Technical data
Communication protocol
Collective / Conventional
Operating voltage
DC 16…28 V
Operating current (quiescent)
Max. ~100 μA
Ext. alarm indicator
2
Operating temperature
-10+50 °C
Storage temperature
-30+70 °C
Humidity
96 % rel.
Color
white, ~RAL 9010
Protection category EN 60529/IEC 60529
with detector base seal RS720
IP40
IP42
System compatibility C-NET
FS720
Standards
CEA4021 / EN 54-7
Dimensions (detector with base)
Ø117 x 62 mm (incl. base)
Approvals
VdS 212059, LPCB request
OP110
Smoke detector (collective)
Part no.
S54372-F4-A1
Documents
Product data sheet
A6V10301051
Techn. description
A6V10316298
Scope of delivery
Detector and dust cap
Application
For the detection of smoke-generating flaming and smoldering fires.
Function
Works according to the scattered light principle with one sensor, optical forward scattering.
Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke
particles.
Selectable detection behavior by 2 parameter sets: Parameter set 1 (Standard); Parameter set 2 (Sensi-
tive)
Technical data
Communication protocol
Collective / Conventional
Operating voltage
DC 16…28 V
Operating current (quiescent)
Max. ~100 μA
Ext. alarm indicator
2
Operating temperature
-10+55 °C
Storage temperature
-30+70 °C
Humidity
96 % rel.
Color
white, ~RAL 9010
Protection category EN 60529/IEC 60529
with detector base seal RS720
IP40
IP42
System compatibility C-Net
FS720
Standards
EN 54-7
Dimensions (detector with base)
Ø117 x 56 mm (incl.base)
Approvals
VdS G212033, LPCB request
60
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc
CPS Fire Safety 04.2014