User Manual
Conventional and collective devices
DMA1192-AA
Housing red with glass and key
Part no.
BPZ:5222870001
DMA1192-AB
Housing yellow with glass and key
Part no.
BPZ:5464250001
DMA1192-AC
Housing blue with glass and key
Part no.
BPZ:5464120001
DMA1192-AD
Housing green with glass and key
Part no.
BPZ:5090190001
DMA1103D
Switching unit collective
Part no.
A5Q00004470
DMA1104D
Switching unit collective
Part no.
A5Q00005925
Document
Product data sheet
007980
DMA1103D
DMA1104D
Application
Collective manual call point for the immediate manual actuation of a fire alarm. For indoor and outdoor
application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines
in easily accessible places. For the connection on the collective/SynoLINE600 detector line. An LED
always indicates the status of the manual call point.
The housing DMA1192-xx and the electronic unit DMA1103D must be ordered separately.
Function
DM1103
Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the
glass plate, open the housing door with the key. The push button must be set back before closing the
door again.
DM1104
Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door
with the key, upon closing the door the button is reset.
Technical data
Communication protocol
collective/SynoLINE600
Operating voltage
DC 16…26 V
Operating current
60…100 mA
Anschlussklemmen
0,28…1,5 mm
2
Einsatztemperatur
-25…+70 °C
Storage temperature
-30…+75 °C
Humidity
≤95 % rel.
Color
red, ~RAL 3000, blue, ~RAL 5005,
yellow, ~RAL 1023, green, ~RAL 6024
Protection category EN 60529/IEC 60529
– mit Dichtung DMZ1197-AD
IP54
IP65
Standard
EN 54-11
Dimensions
134 x 134 x 43 mm
Approvals
– DM1103
– DM1104
VdS G295036
VdS G299068, LPCB 531j/02