8.6 Conventional FDM1101A manual call points
FDM1101A-RG
Manual call point with glass plate
Part no.
S54371-F6-A3
FDM1101A-RP
Manual call point with resettable plastic element
Part no.
S54371-F6-A4
Documents
Product data sheet
A6V10206486
Technical description
A6V10201152
Application
For immediate manual actuation of a fire alarm. For indoor and outdoor application. For surface- and
recess-mounted feed lines in easily accessible places.
For surface mounting the housing base FDMH295-x must be ordered separately.
Function
FDM1101A-RG
Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset
and the device is ready for operation again.
FDM1101A-RP
Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device
is ready for operation again.
Technical data
Communication protocol
conventional
Operating voltage
max. AC 28 V or DC 28 V
Operating current
100 mA…max. 1 A
Terminal block
0.28…1.5 mm²
Operating temperature
-25…+70 °C
Storage temperature
-30…+75 °C
Humidity
≤95 % rel. (no condensation)
Protection category EN 60529/IEC 60529
IP44
Standard
EN 54-11
Color
red, ~RAL 3000
Dimensions
87 x 87 x 20 mm
Approvals
– FDM1101A-RG
– FDM1101A-RP
VdS 209149, LPCB 126as/03
VdS 209149, LPCB 126as/04
FDMH295-R
Back box
Part no.
A5Q00013437
FDMH295-S
Back box with holes and socket
Part no.
A5Q00013438
Details see chapter 4.2
FDMH295-R
FDMH295-S