8.8 Air sampling smoke detection kit FDBZ292
FDBZ292
Air sampling smoke detection kit
Part no.
A5Q00021362
Documents
Product data sheet
009728
Installation
009726
Application
Reliable monitoring of fresh air, used air and air re-circulation ducts for smoke in air conditioning and
ventilation systems.
The smoke detector DO1104A and the base DB1101A must be ordered separately.
Function
The air sampling smoke detection kit is mounted in the ventilation system where air flow measuring
devices are usually installed, i.e. where there is no air vortex, change of direction, duct branching, duct
narrowing or duct extensions. The distance to the branching, bracket or bend must have 5 x the duct
diameter. In order to guarantee smoke detection, mount on the outside of the air duct sampling, after the
last air inlet. Accessories for all shapes of duct.
Technical data
Smoke detector
DO1104A
Detector base
DB1101A
System compatibility
collective/SynoLINE600, in C-NET via Transpon-
der FDCIO223
Min. duct diameter
100 mm
Permissible air speed
1…20 m/s
Air flow indicator
≥1 m/s
Ambient temperature
-20…+50 °C
Dimensions (WxHxD)
146 x 235 x 183 mm
Color
grey, ~RAL 7001
Protection category
IP54
Humidity
≤95 % rel.
8.8.1 Accessories FDBZ292
DO1104A
Smoke detector, collective wide spectrum
Part no.
BPZ:5090640001
Documents
Product data sheet
001578
Technical description
1001
Application
Automatic fire detector with higher response sensitivity for the early warning of smoke-forming, flaming
fires and smoldering fires.
The base DB1101A must be ordered separately.
Technical data
Communication protocol
collective/SynoLINE600
Operating voltage
DC 16…24 V
Quiescent current
max. 100 μA
Operating temperature
-25…+60 °C
Sensitivity
typ. 1.8 %/m
Protection category
IP44
Color
white, ~RAL 9010
Dimensions (ØxH)
115 x 51 mm (incl. base)
Standard
EN 54-7
Approval
VdS G297038