User Manual

Conventional and collective devices
8.9 Conventional alarm devices
8.9.1 Alarm devices AGT24.1, RoLP/R/S, ROLP/W/S
RoLP/R/S
RoLP/W/S
Alarm device
Part no.
GBI:1082507
GBI:1082508
Document
Product data sheet
A6V10423405
Application
For inside and outdoor applications. For general signaling in fire use. Removable base for simple
surface mounting. Adapter base for cable entry with screwed cable gland. Red or white ABS plastic
housing.
Function
Powerful alarm - recognizable as a danger signal even against a high background noise level.
32 different tones programmable (user selectable). Adjustable sound intensity, improved tone clarity,
automatic synchronization. Second input for secondary tone in two stage alarm systems.
Technical data
Operating voltage
DC 1828 V
Alarm current
12 mA
Operating temperature
-25…+70 °C
Tones
32
Sound level
102 dB(A)
Cable capacity
0.28…1.5 mm²
Protection category EN 60529/IEC 60529
with DAB-R/ DAB-W
IP54
IP65
Dimensions
Ø93 x 63 mm
Color
Red, white
DAB-R
DAB-W
Adapter base
Part no.
S54370-N27-A1
S54370-N27-A2
Document
Product data sheet
A6V10423405
Application
Deep base for surface wiring for all types of RoLP sounders for a higher protection category.
Technical data
Protection category EN 60529/IEC 60529
IP65
Color
White or red
Dimensions
Ø93 x 50 mm
76
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc
CPS Fire Safety 04.2014