User Manual
Conventional and collective devices
8.10 Devices for explosion-hazard area of zones 1 and 2
8.10.1 Interface for connection of the 'Ex' devices to C-NET
FDCIO223
Transponder
Part no.
S24218-B102-A1
Documents
Product data sheet
009168
FDCIO223
Technical description
009122
Application
For connection of collective fire detectors (GMT/conventional line, GMT/conventional line with shunt-
Zener-diode barrier (SB3) for explosion-hazard areas).
Accessories and spare parts for FDCIO223 see chapter 6.4.1 and 6.4.2.
Technical data
Operating voltage C-NET
DC 12…33 V
Communication protocol
C-NET
External power supply: Input voltage
DC 18…32 V
In-/outputs as collective detector line
collective GMT Siemens/Cerberus, Synova con-
ventional/SynoLINE300, collective/SynoLINE600
or similar
Collective line factor (KLK)
32
Operating temperature
-25…+60 °C
Storage temperature
-30…+65 °C
Humidity
≤95 % rel.
Connection terminals
0.2…1.5 mm
2
(Auxiliary terminal 2.5 mm
2
)
Color housing / cover
white, ~RAL 9010 / transparent mAtt
Protection category EN 60529/IEC 60529
– with auxiliary housing FDCH221
IP30
IP65
System compatibility C-NET
FS720
Standards
CEA GEI I-084, EN 54-17, EN 54-18
Dimensions
132 x 90 x 24 mm
Approvals
VdS G206054, LPCB 531m/03
80
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc