User Manual
Conventional and collective devices
8.10.2 Interface for connection of 'Ex' devices to SynoLINE600
DCA1191
Housing with cover
Part no.
BPZ:4588560001
DCA1192A
Electronic unit, SynoLINE600
Bestell-Nr.
BPZ:5081200001
DCB1192A
Terminal base
Bestell-Nr.
BPZ:5084500001
Documents
Product data sheet
001571
DCA1191
DCA1192A
DCB1192A
Technical description
1519
Application
The input/output module DC1192 for galvanic isolation (detection line coupler) between control unit of
collective line SynoLINE600 and shunt Zener diode barrier with fire detectors for explosion-hazard
areas (via SB3).
The housing DCA1191, the terminal base DCB1192A and the electronic unit DCA1192A must be or-
dered separately.
Technical data
Primary line -> collective/SynoLINE600
– Compatibility
E3M080, CI1110/15, FC330A, FC10, FC700A,
CZ10, KB24, GF24
Secundary line -> collective/SynoLINE600
– Operating voltage
DC 18…22 V
– Operating current
max. 5 mA
– Line resistance, depends on the type of line
50…250 Ω
– End-of-line unit
EOL22 (Ex)
– Line factor (KLK)
25
Connection terminals
0.2…2.5 mm²
(AWG24…14)
External supply: Operating voltage
DC 18…32 V
Operating temperature
-25…+70 °C
Storage temperature
-30…+75 °C
Humidity
≤95 % rel.
Color housing
white, ~RAL 9010
Schutzart EN 60529 / IEC 60529 mit DCA1191
IP56
Standards
EN 54-17, EN 54-18
Dimensions
135 x 135 x 65 mm
Approvals
VdS G298021, LPCB 126bm/02
EOL22(Ex)
End-of-line
Part no.
BPZ:5162220001
Application
End-of-line unit for collective detection lines as well as generally as end-of-line unit within explosion-
hazard areas of zones 1 and 2.
81
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc