Conventional and collective devices
8.10.3 Shunt Zener diode barrier SB3
SB3
Shunt Zener diode barrier
Part no.
BPZ:4837400001
Document
Product data sheet
001222
Application
This barrier is needed for an intrinsically safe installation in explosion-hazard areas connected to the in-
/output module. This barrier restricts the electrical energy between non-intrinsically safe and intrinsically
safe circuits. The installation has to be done according to the national safety regulations. The SB3 has to
be mounted into the housing DCA1191 together with the Z3I410 installation set.
Always install shunt Zener diode barriers outside explosion-hazard areas.
Technical data
Operating voltage
max. DC 28 V
Operating current
max. 100 mA
Type
Stahl 9001/00-280-100-101
Standard
EN 50014 (IEC 60079-0)/
EN 50020 (IEC 60079-11)
8.10.3.1 Accessories for SB3
DCA1191
Housing with cover
Part no.
BPZ:4588560001
Application
For surface mounting in humid, wet areas.
One Shunt Zener diode barrier SB3 can be built into the housing.
Technical data
Protection category EN 60529/IEC 60529
IP56
Dimensions
135 x 135 x 65 mm
Color
white, ~RAL 9010
Z3I410
Installation set
Part no.
BPZ:4837660001
Application
One SB3 shunt Zener diode barrier mAy be mounted together with support plate Z3I410 in housing
DCA1191 with protection category IP56.
DBZ1190-AA
Micro terminal
Part no.
BPZ:4677080001
Details see chapter 2.2.1
Metall-Kabelverschraubung M20 x 1,5
Part no.
A5Q00004478
Details see chapter 2.3.1