User Manual
Conventional and collective devices
8.10.7 Alarm indicators FDAI92-Ex, FDAI93-Ex
FDAI92-Ex
Alarm indicator (wall mounting)
Part no.
S54370-F4-A1
Document
Product data sheet
A6V10276518
Application
Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the
source of an alarm signal from detectors, which are not easily accessible or visible.
For recess supply line. For surface supply line use adapter frame AI330.
Function
The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm.
Only one external alarm indicator mAy be connected to each detector.
Technical data
Operating voltage
DC 4…5 V
Operating current, dauernd
max. 35 mA
Screwless connection terminals
Wire cross-sectional area max. 1.5 mm
2
Environmental temperature
-25…+80 °C
Ex-classification
'simple apparatus' acc. EN 50020 § 5.4
Ex ib IIC T4 (Ta ≤70 °C)
Humidity
≤95 % rel.
Protection category EN 60529/IEC 60529
IP40
Approvals
EECS, ESTI
Color
white, ~RAL 9010
Dimensions
85 x 85 x 28 mm
8.10.7.1 Accessory for FDAI92-Ex
AI330
Adapter frame
Part no.
BPZ:3169430001
Application
For surface laid conduit or ducts, to increase the loop space or as an adapter for different mAkes of box.
Technical data
Color
white, ~RAL 9010
Dimensions
85 x 85 x 16 mm
89
Building Technologies
058_FD720_Equipment_overview_A6V10225323_j_en.doc
CPS Fire Safety 04.2014