Installation Instructions
A6V11415283_enUS_b
13
FIND FCL2004 SOFTWARE VERSION
To see the firmware version of an installed FCL2004 module, there are two possibilities.
First, one can either transfer the configuration from the panel to the engineering tool. This will populate
various fields including the firmware version as shown in the following figure:
Alternatively, one can query the panel directly. Select the menu Topology -> Hardware Tree. Then
select the panel hosting the FCL2004 card. This will bring the list of all the modules on that panel.
Among these, select the FCL2004 card and by clicking the More Options button, select Execute
Commands-> Report SW version. Then the firmware version will appear on the screen.
COMPATIBILITY
1. The FCL2004 supports only the intelligent devices listed in Table 1 and Table 2. The
compatibility identifiers for the compatible devices are the model numbers listed in Table 1.
Use any combination of those listed. ICPS, however, must be addressed between 1 and 12.
2. The FCL2004 supports two device loops of up to 60 intelligent field devices each. Each loop
draws a maximum of 90mA from the FCL2004.
3. All circuits are power limited per NEC 760. The FCL2004 supports the use of 12-18 AWG non-
shielded, non-twisted, thermoplastic fixture wire without conduit, if permitted by local building
codes.
4. No end of line device is required.
5. Total circuit resistance of each zone must not exceed 100 ohms.
Maximum capacitance:
0.4μF
between
loop+
and loop-
0.8μF
between
loop+
and chassis
0.8μF
between loop- and chassis
6. Does not support P2 (H-Series) devices.
7. Alarm verification shall not be used in initiating device circuits intended for cross-zone operation.