Installation Instructions
A6V11415283_enUS_b
3
Element
Description
Function
Indicators
POWER (Green)
Normally ON. When
illuminated, indicates the
power for the FCL2004 is
applied to the card.
CARD FAIL (Yellow)
Normally OFF. When
illuminated, indicates
hardware failure on the card
or unsuccessful firmware
upload. During firmware
upload, this LED should
blink.
FW UPDATE (Yellow)
Normally OFF. When
illuminated, indicates that
the FCL2004 is being
updated through the PMI.
DEGRADE ALARM (Red)
Normally OFF. When
illuminated, the ALD has
detected an ALARM, but is
unable to communicate with
the PMI.
TROUBLE (Yellow)
Normally OFF. When
illuminated, the ALD has
detected a Trouble. Only
specific ALD circuit troubles
such as Degrade Trouble,
Card Failure, Ground Fault,
or Circuit Fault will trigger
this LED.
LOOP FAULT (Yellow)
Normally OFF. When
illuminated, indicates that
the FCL2004 has detected a
wiring trouble (fault) on
device loop 1 or 2.
GND FAULT (Yellow)
Normally OFF. When
illuminated, indicates that
the FCL2004 has detected a
ground fault on device loop
1 or 2 field wiring.
Adjustment elements
S30
Reset button
Connectors
X200
Detector circuit (Loop 1)
X201
Detector circuit (Loop 2)
X500
(24 VDC) Pin2 Pin1 from
Periboard X1001; Pin4 Pin3
to next FCL2004 or device.
X503
CZM power output
X600
From PMI X11
X601
To X601 of next FCL2004
Jumpers
J8
Audible base switch (EN 1,
2) (DIS 2, 3)
JP4
ALD GND Fault Enable
X300
WatchDog On/Off