Operating Instructions
Table Of Contents
- Fire Alarm Control Panel
- Model FC901
- TABLE OF CONTENTS
- INTRODUCTION
- DESCRIPTIONS
- SLC grounding detection threshold
- CONTROL PANEL OPERATION
- CONTROL PANEL INSTALLATION
- SYSTEM WIRING
- AC Connection
- Battery Connection
- WIRING
- Control Panel Wiring Overview
- Wiring Entering Enclosure
- Install Wiring
- Wiring Separation
- Internal Structure
- Power Supply and Battery Wiring
- Status Relays
- Auxiliary Power Outputs Wiring
- NAC Wiring
- Serial Interface Circuit (UFP)
- Serial Remote Device Wiring Overview
- SLC Addressable Device Circuit
- SLC Addressable Device Wiring Diagrams
- Optional City Tie/Leased Line
- DACT Wiring
- PROGRAMMING THE CONTROL PANEL
- MAINTENANCE
- APPENDIX-A: REFERENCE DATA
- APPENDIX-B: COMPATIBLE DEVICES
- APPENDIX-C: TROUBLESHOOTING
- APPENDIX-D: ALARM VERIFICATION
- APPENDIX-E: APPLICATION SPECIFIC DETECTION
- APPENDIX-F: TESTING/MAINTENANCE
- APPENDIX-G: LCD, CONTROLS AND INDICATORS
- APPENDIX-H: OUTPUT FEATURES
- APPENDIX-I: PAS / PRE-SIGNAL
- APPENDIX-J: DACT INFORMATION OVERVIEW
- APPENDIX-K: DRIFT COMPENSATION
- APPENDIX-L: RELEASING OPERATION
- APPENDIX-M: GLOSSARY
- APPENDIX-N: PAD-4 WIRING INSTRUCTION
- APPENDIX-O: ISOLATOR SUPPORT
8
The information of the rest annunciators is displayed in the below table:
Product
Zones
System status LEDs
Buttons
FT2008-U1/R1
16
7
Audibles On/Silenced
Acknowledge
Signal Reset
Lamp Test
FT2009-U1/R1
32
7
Audibles On/Silenced
Acknowledge
Signal Reset
Lamp Test
FT2018-U1/R1
16
6
N/A
FT2019-U1/R1
32
6
N/A
Up to 8 annunciators may be addressed by the communication circuit. Each annunciator
requires connection to the Serial Interface circuit on the mainboard.
For installation in Canada, the FT2018-U1/R1 or FT2019-U1/R1, only one can be and
must be installed adjacent to the panel and interconnection must be in metallic conduit.
For installation in Canada, a separate ULC listed power supply (PAD-4 or PAD-5) must
be installed adjacent to the FC2005 or FC901 panel to power the FT2018-U1/R1 or
FT2019-U1/R1 annunciator. See Appendix N for PAD-4 Wiring Instruction.
When configuring the FT2018-U1/R1 or FT2019-U1/R1 for Canadian applications, it must
be programmed as a local device so that lamp test can be initiated from panel.
When annunciator FT2018-U1/R1 or FT2019-U1/R1 is connected to a Canadian panel,
the buzzer on the panel must be disabled (panel buzzer ON must be unchecked)
Battery Housing (FH2072-UA)
FH2072-UA is used to install batteries separately. Supported batteries are: 12 Ah for Canada
and 12 - 18 Ah for US.
Universal Enclosure for Annunciators (FTH2073-UA)
FTH2073-UA is used to install annunciators.
Supported annunciators are: FSD901, FT2008, FT2009, FT2018 and FT2019.