Operating Instructions
Table Of Contents
- Fire Alarm Control Panel
- Model FC901
- TABLE OF CONTENTS
- INTRODUCTION
- DESCRIPTIONS
- SLC grounding detection threshold
- CONTROL PANEL OPERATION
- CONTROL PANEL INSTALLATION
- SYSTEM WIRING
- AC Connection
- Battery Connection
- WIRING
- Control Panel Wiring Overview
- Wiring Entering Enclosure
- Install Wiring
- Wiring Separation
- Internal Structure
- Power Supply and Battery Wiring
- Status Relays
- Auxiliary Power Outputs Wiring
- NAC Wiring
- Serial Interface Circuit (UFP)
- Serial Remote Device Wiring Overview
- SLC Addressable Device Circuit
- SLC Addressable Device Wiring Diagrams
- Optional City Tie/Leased Line
- DACT Wiring
- PROGRAMMING THE CONTROL PANEL
- MAINTENANCE
- APPENDIX-A: REFERENCE DATA
- APPENDIX-B: COMPATIBLE DEVICES
- APPENDIX-C: TROUBLESHOOTING
- APPENDIX-D: ALARM VERIFICATION
- APPENDIX-E: APPLICATION SPECIFIC DETECTION
- APPENDIX-F: TESTING/MAINTENANCE
- APPENDIX-G: LCD, CONTROLS AND INDICATORS
- APPENDIX-H: OUTPUT FEATURES
- APPENDIX-I: PAS / PRE-SIGNAL
- APPENDIX-J: DACT INFORMATION OVERVIEW
- APPENDIX-K: DRIFT COMPENSATION
- APPENDIX-L: RELEASING OPERATION
- APPENDIX-M: GLOSSARY
- APPENDIX-N: PAD-4 WIRING INSTRUCTION
- APPENDIX-O: ISOLATOR SUPPORT
13
Device type supervision: If the device type identifier reported by an addressable detector or
module does not agree with the configuration, the system reports a trouble condition.
Device address supervision: The system checks that all configured devices on the addressable
device circuit respond to an address poll. The system reports a trouble condition if the
following conditions are detected:
◼ Configured device is missing.
◼ Unconfigured device is installed.
◼ Two devices are programmed with the same address.
◼ Signaling line circuit experiences a wire-to-wire short.
◼ Signaling line circuit experiences an earth ground condition.
REGULATORY STANDARDS
The FC901 control panel meets the requirements of industry and government regulatory
agencies as noted.
Underwriters Laboratories
The FC2005 control panel is listed under UL 864 (Tenth Edition) and to be installed in
Accordance with the applicable National Fire Protection Association Installation Standard for
NFPA 72 and NFPA 2001.
Underwriters Laboratories of Canada
The FC2005 control panel is listed under ULC-S527-11 (Third Edition) Amendment 1, and to
be installed in accordance with CSA C22.1-06, Canadian Electrical Code, CAN/ULC-S524,
Installation of Fire Alarm Systems, CAN/ULC-S536, Inspection and Testing of Fire Alarm
Systems.
Federal Communications Commission
The DACT meets the Class A requirements of the Code of Federal Regulations (CFR 47), Part
15 for electromagnetic field emissions. The DACT also meets the requirements of the Code of
Federal Regulations (CFR 47), Part 68, for connection of equipment to the public switched
telephone network.