The auxiliary power of control panel supervises only the short circuit and ground circuit.
The open circuit is not included. To supervise the open circuit, a PAD-5 device power
must be used.
When using an annunciator with the 50pt. panel, use the non-resettable power supplied
from the Fire Alarm Control Panel (FACP). When the annunciator is located too far from
the FACP use a Battery backed up UL approved Power Supply to ensure continuous and
proper operation.