Operating Instructions
Table Of Contents
- Fire Alarm Control Panel
- Model FC901
- TABLE OF CONTENTS
- INTRODUCTION
- DESCRIPTIONS
- SLC grounding detection threshold
- CONTROL PANEL OPERATION
- CONTROL PANEL INSTALLATION
- SYSTEM WIRING
- AC Connection
- Battery Connection
- WIRING
- Control Panel Wiring Overview
- Wiring Entering Enclosure
- Install Wiring
- Wiring Separation
- Internal Structure
- Power Supply and Battery Wiring
- Status Relays
- Auxiliary Power Outputs Wiring
- NAC Wiring
- Serial Interface Circuit (UFP)
- Serial Remote Device Wiring Overview
- SLC Addressable Device Circuit
- SLC Addressable Device Wiring Diagrams
- Optional City Tie/Leased Line
- DACT Wiring
- PROGRAMMING THE CONTROL PANEL
- MAINTENANCE
- APPENDIX-A: REFERENCE DATA
- APPENDIX-B: COMPATIBLE DEVICES
- APPENDIX-C: TROUBLESHOOTING
- APPENDIX-D: ALARM VERIFICATION
- APPENDIX-E: APPLICATION SPECIFIC DETECTION
- APPENDIX-F: TESTING/MAINTENANCE
- APPENDIX-G: LCD, CONTROLS AND INDICATORS
- APPENDIX-H: OUTPUT FEATURES
- APPENDIX-I: PAS / PRE-SIGNAL
- APPENDIX-J: DACT INFORMATION OVERVIEW
- APPENDIX-K: DRIFT COMPENSATION
- APPENDIX-L: RELEASING OPERATION
- APPENDIX-M: GLOSSARY
- APPENDIX-N: PAD-4 WIRING INSTRUCTION
- APPENDIX-O: ISOLATOR SUPPORT
47
SLC ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA CLASS X
(or PABE DCLC)
CLASS X (DCLC) provides redundant communication paths.
- S_AN
+ S_AP
- S_BN
+ S_BP
SEE NOTE SEE NOTE
SEE
NOTE
SEE
NOTE
ISOLATOR
MODULE
SEE NOTE
SEE NOTE SEE NOTE
SEE
NOTE
SEE NOTE
SUPERVISED
POWER LIMITED
PORT-A PORT-B
NOTE
• Siemens SLC Devices: Monitor Modules, or Control Modules up to a maximum of 50 devices.
• Only listed Class X (DCLC) devices, models XTRI-R, XTRI-D, XTRI-S, XTRI-M, ILED-XW, ILED-XC,
TSM-1X, and PAD-5 can support CLASS X (DCLC) mode. And all these devices must be wired as
isolator modules. If Class X (DCLC) devices are mixed with existing devices or wired as non-
isolator modules, only Class A (DCLA) supervision can be achieved.