- DESCRIPTIONS
- SLC grounding detection threshold
- CONTROL PANEL OPERATION
- CONTROL PANEL INSTALLATION
- SYSTEM WIRING
- AC Connection
- Battery Connection
- WIRING
- Control Panel Wiring Overview
- Wiring Entering Enclosure
- Install Wiring
- Wiring Separation
- Internal Structure
- Power Supply and Battery Wiring
- Status Relays
- Auxiliary Power Outputs Wiring
- NAC Wiring
- Serial Interface Circuit (UFP)
- Serial Remote Device Wiring Overview
- SLC Addressable Device Circuit
- SLC Addressable Device Wiring Diagrams
- Optional City Tie/Leased Line
- DACT Wiring
- PROGRAMMING THE CONTROL PANEL
- MAINTENANCE
- APPENDIX-A: REFERENCE DATA
- APPENDIX-B: COMPATIBLE DEVICES
- APPENDIX-C: TROUBLESHOOTING
- APPENDIX-D: ALARM VERIFICATION
- APPENDIX-E: APPLICATION SPECIFIC DETECTION
- APPENDIX-F: TESTING/MAINTENANCE
- APPENDIX-G: LCD, CONTROLS AND INDICATORS
- APPENDIX-H: OUTPUT FEATURES
- APPENDIX-I: PAS / PRE-SIGNAL
- APPENDIX-J: DACT INFORMATION OVERVIEW
- APPENDIX-K: DRIFT COMPENSATION
- APPENDIX-L: RELEASING OPERATION
- APPENDIX-M: GLOSSARY
- APPENDIX-N: PAD-4 WIRING INSTRUCTION
- APPENDIX-O: ISOLATOR SUPPORT
61
APPENDIX-C: TROUBLESHOOTING
DEFINITIONS FOR EVENT HISTORY ENTRIES
A. General
ENTRY
INDICATES
Disabled
The device has been disabled
Ground
The device is in ground fault
Open
The device is in open trouble
Short
The device is in short trouble
Overload
The SLC line is overloaded
GeneralTrouble
The device reports general trouble
Unconfig
The system finds a SLC device that is not in the config file
TypeMismatch
The SLC device type is not consistent with the config file
CommunicationTrouble
The communication between the device and the panel is abnormal
Multiple Device Response
More than one SLC device has the same address
TypeUnknown
The device type is unknown to the panel
Dirty
The SLC device is dirty
Replace
The SLC device needs to be replaced
ParameterError
The SLC device has invalid parameter setting
AddressInvalid
The address of SLC device is invalid
AddressUnspecified
The SLC device has no address
ACFail
The AC power of the system is in trouble
MessageLost
The DACT lost some messages because of limited memory space
FatalFault
The SLC device reported fatal fault trouble
VoltageLow
The battery voltage is too low
VoltageHigh
The battery voltage is too high
OverCurrent
The NAC is in over current state
CircuitTrouble
The battery charge circuit is in trouble
BatteryAbsent
The battery is missing