Operating Instructions
Table Of Contents
- Fire Alarm Control Panel
- Model FC901
- TABLE OF CONTENTS
- INTRODUCTION
- DESCRIPTIONS
- SLC grounding detection threshold
- CONTROL PANEL OPERATION
- CONTROL PANEL INSTALLATION
- SYSTEM WIRING
- AC Connection
- Battery Connection
- WIRING
- Control Panel Wiring Overview
- Wiring Entering Enclosure
- Install Wiring
- Wiring Separation
- Internal Structure
- Power Supply and Battery Wiring
- Status Relays
- Auxiliary Power Outputs Wiring
- NAC Wiring
- Serial Interface Circuit (UFP)
- Serial Remote Device Wiring Overview
- SLC Addressable Device Circuit
- SLC Addressable Device Wiring Diagrams
- Optional City Tie/Leased Line
- DACT Wiring
- PROGRAMMING THE CONTROL PANEL
- MAINTENANCE
- APPENDIX-A: REFERENCE DATA
- APPENDIX-B: COMPATIBLE DEVICES
- APPENDIX-C: TROUBLESHOOTING
- APPENDIX-D: ALARM VERIFICATION
- APPENDIX-E: APPLICATION SPECIFIC DETECTION
- APPENDIX-F: TESTING/MAINTENANCE
- APPENDIX-G: LCD, CONTROLS AND INDICATORS
- APPENDIX-H: OUTPUT FEATURES
- APPENDIX-I: PAS / PRE-SIGNAL
- APPENDIX-J: DACT INFORMATION OVERVIEW
- APPENDIX-K: DRIFT COMPENSATION
- APPENDIX-L: RELEASING OPERATION
- APPENDIX-M: GLOSSARY
- APPENDIX-N: PAD-4 WIRING INSTRUCTION
- APPENDIX-O: ISOLATOR SUPPORT
68
Communication Port Connector
The communication port is connected to the USB port of the computer that has the FXS901-U2
programming tool. This is used to upload and/or download panel configuration if this method of
programming is used.
The computer must be disconnected from the panel if not in use.
LEDS, Buzzer and Dedicated Push Buttons
The LEDs operate as follows:
Item
LED
Color
Status
Description
1
Alarm
Red
Steady ON
There are alarm events, and all alarm events
have been acknowledged.
OFF
There is no alarm event in system.
Flashing
There are alarm events in system, but some
of them have not been acknowledged.
2
Power
(US)
Power On
(Canada)
Green
Steady ON
The system's power works normally. Both
the main power and battery are in normal
status.
OFF
The system is not powered on. This LED can
be OFF only when the system is shut down.
Flashing
The main power is in trouble and system is
powered via battery.
3
Silenced
(US)
Signal
Silence
(Canada)
Yellow
Steady ON
All outputs which can be silenced are
silenced.
OFF
There are no silenced outputs in system.
Flashing
Both silenced and unsilenced outputs exist.
4
Trouble
Yellow
Steady ON
There are trouble events, and all of them
have been acknowledged.
OFF
There is no trouble event in system.
Flashing
There are trouble events in system, but
some of them have not been acknowledged.
5
Supervisory
Yellow
Steady ON
There are supervisory events, and all of
them have been acknowledged.
OFF
There is no supervisory event in system.
Flashing
There are supervisory events in system, but
some of them have not been acknowledged.
6
Ground Fault
Yellow
Steady ON
There are Ground Fault events in system.