Operating Instructions

Table Of Contents
69
OFF
There is no Ground Fault event in system.
Flashing
There are ground fault events in system, but
some of them have not been acknowledged.
7
Audible
On (US)
Alarm
Signal
Activation
(Canada)
Red
Steady ON
The LED 7 can only be steady on when any
of the following conditions are met:
1. There are activated NACs and some of
them are not silenced.
2. There are silenceable devices activated
and some of them are not silenced.
OFF
The LED 7 will be OFF when above
conditions are not met.
The buzzer operates as follows:
Normally OFF indicates that the system is in normal condition or all events in the system
have been acknowledged.
ON (200 pulse per minute) indicates that at least ONE unacknowledged alarm is present in
the system.
ON (85 pulse per minute) indicates that at least ONE unacknowledged non-alarm (trouble,
supervisory) event is present in the system.
The buttons operates as follows:
Item
Button
Action
Description
8
Programmable (US)
Press
Press button 8 to execute user defined and configured
functions.
Alarm Signal Activation
(Canada)
Press button 8 to report the alarm zone events to the
panel.
9
Silence/Unsilence (US)
Press
The button toggles between silence and unsilence.
Press button 9 to silence the audible and/or visual
notification appliances (where permitted by the codes
and control panel programming). The notification
appliances will be de-activated, and the LED 3 will be
off. Press button 9 again to unsilence the previously
silenced notification appliances.
Signal Silence/Unsilence
(Canada)
10
Acknowledge/Buzzer Silence
Press
Acknowledges all unacknowledged events in system.
17
Reset
Press
Clears all obsolete events and resets all devices, except
those disabled ones and hold-through-reset devices in
system.
11
C
Press
Cancel button for PMI operation.
12
OK
Press
OK button for PMI operation.
13
*
Press
* button for PMI operation.
14
#
Press
# button for PMI operation.
15
0-9
Press
Numeric buttons for PMI operation. They are used to
enter the password to access the maintenance and
technician modes of the panel. It allows the user to
program the panel using these keypads without using
the FXS901-U2 programming tool.