Operating Instructions
Table Of Contents
- Fire Alarm Control Panel
- Model FC901
- TABLE OF CONTENTS
- INTRODUCTION
- DESCRIPTIONS
- SLC grounding detection threshold
- CONTROL PANEL OPERATION
- CONTROL PANEL INSTALLATION
- SYSTEM WIRING
- AC Connection
- Battery Connection
- WIRING
- Control Panel Wiring Overview
- Wiring Entering Enclosure
- Install Wiring
- Wiring Separation
- Internal Structure
- Power Supply and Battery Wiring
- Status Relays
- Auxiliary Power Outputs Wiring
- NAC Wiring
- Serial Interface Circuit (UFP)
- Serial Remote Device Wiring Overview
- SLC Addressable Device Circuit
- SLC Addressable Device Wiring Diagrams
- Optional City Tie/Leased Line
- DACT Wiring
- PROGRAMMING THE CONTROL PANEL
- MAINTENANCE
- APPENDIX-A: REFERENCE DATA
- APPENDIX-B: COMPATIBLE DEVICES
- APPENDIX-C: TROUBLESHOOTING
- APPENDIX-D: ALARM VERIFICATION
- APPENDIX-E: APPLICATION SPECIFIC DETECTION
- APPENDIX-F: TESTING/MAINTENANCE
- APPENDIX-G: LCD, CONTROLS AND INDICATORS
- APPENDIX-H: OUTPUT FEATURES
- APPENDIX-I: PAS / PRE-SIGNAL
- APPENDIX-J: DACT INFORMATION OVERVIEW
- APPENDIX-K: DRIFT COMPENSATION
- APPENDIX-L: RELEASING OPERATION
- APPENDIX-M: GLOSSARY
- APPENDIX-N: PAD-4 WIRING INSTRUCTION
- APPENDIX-O: ISOLATOR SUPPORT
88
Releasing indication configuration in Canada
For Canadian applications, LEDs on FT2018 or FT2019 annunciator shall be configured to
indicate pre-discharge, discharge, abort in alarm condition and “invalid abort” trouble in normal
standby condition.
Following is an example of configuration:
Preconditions:
• Releasing control configuration
• LED control configuration
Area configuration
Under the property for Area, there is a setting named “Function”. Two options are
available for it: Normal and Release Trouble Indication. Users can select either one as
needed. Each Area corresponds to one LED zone on the annunciator. Area 1
corresponds to zone 1; Area 2 corresponds to zone 2, etc. By selecting “Normal” or
“Release Trouble Indication”, users get different LED status and different meaning the
LEDs represent. In this case, Area 1 is set to “Release Trouble Indication” and Area 2 is
set to “Normal”:
Area
Function
Corresponding LED
LED color and
status
Description
Normal
3
Predischarge
[flash]/Discharge
[steady]
Red flashing
Pre-discharge status
Red steady
Discharge status
Off
Normal
4
Abort activation
Yellow steady
Abort switch is activated
Off
Abort switch is not activated