Data Sheet for Product

‘08 Series Notification Appliances
2572
s Industry, Inc.
Building Technologies Division
s
CatalogSheet
FireSafety &Security Products
‘08 Series Notification Appliances
CH – Chimes and Chime Strobes
Application: Indoor
Product Overview
Low current draw with temperature compensation to reduce power consumption and wiring costs
Wall-mount models are available with field selectable Candela settings of 15/30/75/110cd
Ceiling-mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd
Strobes produce one (1) flash per second over the regulated input voltage range
Strobes can be synchronized using the Siemens DSC sync modules, FS-250 panel, XLS panel,
or PAD-3 power supply with built-in sync protocol
Adjustable volume and tone control
Single stroke or vibrating operation
Fast Installation with In / Out screw terminals using #12 to #18 AWG wires
UL Listed & ULC Listed;
FM, CSFM & NYMEA Approved
Meets OSHA 29 Part 1910.165
ADA/NFPA/UFC/ANSI compliant
Specifications
Chime appliances shall be Siemens Series CH Chimes, and the chime-strobe appliances shall be
Siemens Series CH Chime Strobes or approved equals
The chime shall be
UL Listed under Standard 464 for Audible Signal Appliances, and chimes equipped
with strobes shall be listed under
UL Standard 1971 for Emergency Devices for the Hearing-Impaired
Strobes shall incorporate low-temperature compensation to ensure the lowest possible current
consumption
All chimes shall use solid state components, and shall provide field-selectable, single-stroke or
vibrating operation with volume and tone control
All models shall have a peak sound output of 83 dBA Anechoic at 10 feet, and an adjustable
frequency range of 800 to 1200 Hz.
All inputs shall employ terminals that accept #12 to #18 AWG wire sizes
Strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the
Regulated Input Voltage Range, and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens
Strobe shall be of low-current design, and where multi-Candela Chime Strobes are specified, the
strobe intensity shall have field-selectable settings and shall be rated per
UL Standard 1971 at:
15/30/75/110cd for wall mount
15/30/75/95cd or 115/177cd for ceiling mount
CH-CW
Chime
CH-R
Chime
CH-MC-R
Chime
Strobe
CH-MC-CW
C
S
trobe

Summary of content (3 pages)