Data Sheet for Product
‘08 Series Notification Appliances
2572
s Industry, Inc.
Building Technologies Division
s
CatalogSheet
FireSafety &Security Products
‘08 Series Notification Appliances
CH – Chimes and Chime Strobes
Application: Indoor
Product Overview
– Low current draw with temperature compensation to reduce power consumption and wiring costs
– Wall-mount models are available with field selectable Candela settings of 15/30/75/110cd
– Ceiling-mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd
– Strobes produce one (1) flash per second over the regulated input voltage range
– Strobes can be synchronized using the Siemens DSC sync modules, FS-250 panel, XLS panel,
or PAD-3 power supply with built-in sync protocol
– Adjustable volume and tone control
– Single stroke or vibrating operation
– Fast Installation with In / Out screw terminals using #12 to #18 AWG wires
–
UL Listed & ULC Listed;
FM, CSFM & NYMEA Approved
– Meets OSHA 29 Part 1910.165
– ADA/NFPA/UFC/ANSI compliant
Specifications
– Chime appliances shall be Siemens Series CH Chimes, and the chime-strobe appliances shall be
Siemens Series CH Chime Strobes or approved equals
– The chime shall be
UL Listed under Standard 464 for Audible Signal Appliances, and chimes equipped
with strobes shall be listed under
UL Standard 1971 for Emergency Devices for the Hearing-Impaired
– Strobes shall incorporate low-temperature compensation to ensure the lowest possible current
consumption
– All chimes shall use solid state components, and shall provide field-selectable, single-stroke or
vibrating operation with volume and tone control
– All models shall have a peak sound output of 83 dBA Anechoic at 10 feet, and an adjustable
frequency range of 800 to 1200 Hz.
– All inputs shall employ terminals that accept #12 to #18 AWG wire sizes
– Strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the
Regulated Input Voltage Range, and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens
– Strobe shall be of low-current design, and where multi-Candela Chime Strobes are specified, the
strobe intensity shall have field-selectable settings and shall be rated per
UL Standard 1971 at:
15/30/75/110cd for wall mount
15/30/75/95cd or 115/177cd for ceiling mount
CH-CW
Chime
CH-R
Chime
CH-MC-R
Chime
Strobe
CH-MC-CW
C
hime
S