Mount the processor unit away from the flow measuring section (e.g. on the wall). Make sure
that condensation cannot run along the connected lines, entering the processor unit (forming
a loop downward).
Permissible mounting position when metering cooling energy:
1 Transducer cover (only applies to WS.6..)
Processor unit
The ambient temperature of the processor unit cannot exceed 55 °C. Avoid direct sunlight.
Ensure that no water can enter the processor unit at the mounting location.
For water temperatures between 10 °C and 90 °C, the processor can be secured to the flow
measuring section.
For water temperatures above 90 °C and/or below 10 °C, mount the processor unit on the
wall (split mounting).
The adapter plate on the wall or the flow measuring section can be aligned as needed to en-
sure ease of reading. To remove the electronic unit, turn the housing by 45° to the side and
lift.
To fit the processor unit to the wall, remove it from the flow measuring section and screw the
adapter plate to the wall and slide the processor unit to the adapter base, snapping into
place.
NOTICE
WS.5..: The adapter plate cannot be removed. The wall adapter must be ordered separate-
ly as an accessory.
WS.6..: The adapter plate can be removed from the flow measuring section.