Data Sheet for Product

s Industry, Inc.
Building Technologies Division
–3–
Cylinder Mounting Straps & Brackets
The steel straps and brackets are used to
mount the cylinders in vertical position:
The brackets, which can be used for wall-
mounting purposes, are secured to adjacent
wall studs.
Liquid Level Indicator
The Liquid Level Indicator operates
magnetically, so there is no need to move or
disconnect cylinders. Uninterrupted hazard
protection is a key feature of the
liquid level
indicator. Additionally, the liquid level
indicator is factory installed.
Low-Pressure Indicating Switch
The Sinorix Low-Pressure Indicating Switch
(Model CPY-PSS1) is a single-pole, single-throw
switch that is mounted to the cylinder valve
during production.
Model CPY-PSS1 will remain in the (NC)
position when no pressure is set against the
switch. In Normal operating position, the Low-
Pressure switch is set at 360 psig. When the
cylinder valve is pressurized, Model CPY-PSS1
will move into the open position.
Upon loss of pressure from the cylinder valve
due to discharge or leakage Model CPY-PSS1
moves to a closed position at 291psig. Model
CPY-PSS1 is monitored by a Supervisory point
on the fire-alarm control panel (FACP). The
FACP provides a Supervisory alarm upon loss of
pressure below the PSIG set point.
Details for Ordering
Model
Part
Number
Description
CPYCS-900 500-649667BG 900 Lbs. Cylinder Strap
CPYEC-2-24 500-697990BG
Supervised
Electronic Solenoid
CPY-LMC2 500-697925BG-2 Local Manual Control Head
CPY-PAS2 500-697926BG-2
Pressure Actuated
Control Head
CPY-900 CPY-900-00-2-xxx
Sinorix 227
Fire Suppression System
CPY-900 CPY-900-00-3-xxx
Sinorix 1230
Fire Suppression System