Cylinder Mounting Straps & Brackets
The steel straps and brackets are used to
mount the cylinders in the vertical position:
The brackets, which are used for wall-
mounting purposes, are secured to adjacent
wall studs. The brackets and straps are UL
Listed & ULC Listed; as well as FM Approved.
Liquid-Level Indicator
The Liquid-Level Indicator works magnetically,
so it is not necessary to move or disconnect
cylinders. Uninterrupted hazard protection is
a key feature:
The Liquid-Level Indicator must be factory
installed, and is UL Listed & ULC Listed;
as well as FM Approved.
Sino rix Liquid-Level Indicator 1 (Cylinder Maintenance)
Low-Pressure Switch
The Sinorix Low-Pressure Indicating Switch
(Model CPY-PSS1) is a single-pole, single-
throw switch that is mounted to the cylinder
valve during production.
Model CPY-PSS1 will remain in the (NC)
position when no pressure is set against the
switch. In Normal operating position, the
Low-Pressure switch must be set at 360 psig.
When the cylinder valve is pressurized, Model
CPY-PSS1 will move into the open position.
Upon loss of pressure from the cylinder valve
due to discharge or leakage Model CPY-
PSS1 will move to a closed position at
291psig. Model CPY-PSS1 is monitored by a
Supervisory point on the fire-alarm control
panel (FACP). The FACP will provide a
Supervisory alarm upon loss of pressure
below the PSIG set point.