Data Sheet for Product

s Industry, Inc.
Building Technologies Division
–3–
Cylinder Mounting Straps & Brackets
The steel straps and brackets are used to mount
the cylinders in the vertical position:
The brackets, which are used for wall-mounting
purposes, are secured to adjacent wall studs.
The brackets and straps are UL Listed & ULC
Listed; as well as FM Approved.
Liquid-Level Indicator
The Liquid-Level Indicator operates magnetically,
so there is no need to move or disconnect
cylinders. Uninterrupted hazard protection is a
key feature:
The Liquid-Level Indicator must be factory
installed, and is UL Listed & ULC Listed;
as well as FM Approved.
Sino rix Liquid-Level Indicator 2 (Cylinder Maintenance)
Low-Pressure Switch
The Sinorix Low-Pressure Indicating Switch
(Model CPY-PSS1) is a single-pole, single-
throw switch that is mounted to the cylinder
valve during production.
Model CPY-PSS1 will remain in the (NC)
position when no pressure is set against the
switch. In Normal operating position, the
Low-Pressure switch is be set at 360 psig.
When the cylinder valve is pressurized,
Model CPY-PSS1 will move into the open
position.
Upon loss of pressure from the cylinder
valve due to discharge or leakage Model
CPY-PSS1 moves to a closed position at
291psig. Model CPY-PSS1 is monitored by a
Supervisory point on the fire-alarm control
panel (FACP). The FACP will provide a
Supervisory alarm upon loss of pressure
below the PSIG set point.