Description: The value influences the rate at which the output frequency is changed during a flying restart . A higher value
results in a longer search time.
Caution: An unfavorable parameter value can result in the motor behaving in an uncontrollable fashion.
For vector control, a value that is too low or too high can cause flying restart to become unstable.
Note: The parameter factory setting is selected so that standard induction motors that are rotating can be found and
restarted as quickly as possible (fast flying restart).
With this pre-setting, if the motor is not found (e.g. for motors that are accelerated as a result of active loads or with
U/f control and low speeds), we recommend that the search rate is reduced (by increasing p1203).
Description: Displays the status for checking and monitoring flying restart states in the U/f control mode.
p1203[0...n] Flying restart search rate factor / FlyRst v_Srch Fact
PM240
PM250, PM260
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
10 [%] 4000 [%] 100 [%]
r1204.0...13 CO/BO: Flying restart, U/f control status / FlyRest Uf st
Access level: 4 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Current impressed Yes No -
01 No current flow Yes No -
02 Voltage input Yes No -
03 Voltage reduced Yes No -
04 Start ramp-function generator Yes No -
05 Wait for execution Yes No -
06 Slope filter act Yes No -
07 Positive gradient Yes No -
08 Current < thresh Yes No -
09 Current minimum Yes No -
10 Search in the positive direction Yes No -
11 Stop after positive direction Yes No -
12 Stop after negative direction Yes No -
13 No result Yes No -