Description: Sets the configuration for the motor data identification.
Note: The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature induc-
tance Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
p1909[0...n] Motor data identification control word / MotID STW
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned16
Can be changed: T Scaling: - Data set: MDS
Units group: - Unit selection: -
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no measure-
ment
Yes No -
02 Rotor time constant estimate no measure-
ment
Yes No -
03 Leakage inductance estimate no measure-
ment
Yes No -
05 Determine Tr and Lsig evaluation in the time
range
Yes No -
06 Activate vibration damping Yes No -
07 De-activate vibration detection Yes No -
11 De-activate pulse measurement Lq Ld Yes No -
12 De-activate rotor resistance Rr measure-
ment
Yes No -
14 De-activate valve interlocking time mea-
surement
Yes No -
15 Determine only stator resistance, valve volt-
age fault, dead time
Yes No -