Technical data

Parameters
List of Parameters
1-292
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: Displays the first status word for monitoring functions.
Notice: Re bit 06:
When the overspeed is reached, this bit is set and F07901 output immediately following this. The bit is canceled
again as soon as the next pulse inhibit is present.
Note: Re bit 00:
The threshold value is set in p1080 and the hysteresis in p2150.
Re bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
Re bit 03:
1 signal direction of rotation positive.
0 signal: direction of rotation negative.
The hysteresis is set in p2150.
Re bit 04:
The threshold value is set in r1119 and the hysteresis in p2150.
Re bit 05:
The threshold value is set in p1266 and the delay time in p1228.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
Re bit 08:
The threshold value is set in p2170 and the delay time in p2171.
Re bit 09, 10:
The threshold value is set in p2172 and the delay time in p2173.
Re bit 11:
The threshold value is set in p2179 and the delay time in p2180.
Re bit 12:
The threshold value is set in p2182, the hysteresis in p2162, and the delay time (for canceling the signal) in p2152.
r2197.0...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| <= n_min p1080 Yes No 8020
01 -
02 -
03 n_act >= 0 Yes No 8011
04 |n_act| >= n_set Yes No 8020
05 |n_act| <= n_standstill p1226 Yes No 8020
06 |n_act| > n_max Yes No 8010
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8011
08 I_act >= I_threshold value p2170 Yes No 8020
09 Vdc_act <= Vdc_threshold value p2172 Yes No 8020
10 Vdc_act > Vdc_threshold value p2172 Yes No 8020
11 Output load is not present Yes No 8020
12 |n_act| > n_max (delayed) Yes No 8021
13 |n_act| > n_max error Yes No -