Technical data

Parameters
List of Parameters
1-30
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: Displays status word 1.
Caution: p2080 is used to define the signal sources of the PROFIdrive status word interconnection.
Note: The following status bits are displayed in r0052.
Bit 00: r0899 Bit 0
Bit 01: r0899 Bit 1
Bit 02: r0899 Bit 2
Bit 03: r2139 Bit 3 (or r1214 Bit 10, if p1210 > 0)
Bit 04: r0899 Bit 4
Bit 05: r0899 Bit 5
Bit 06: r0899 Bit 6
Bit 07: r2139 Bit 7
Bit 08: r2197 Bit 7
Bit 09: r0899 Bit 7
Bit 10: r2197 Bit 6
Bit 11: r0056 Bit 13 (negated)
Bit 13: r2135 Bit 14 (negated)
Bit 14: r2197 Bit 3
Bit 15: r2135 Bit 15 (negated)
r0052.0...15 CO/BO: Status word 1 / ZSW 1
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Rdy for switch on Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
03 Fault present Yes No -
04 Coast down active (OFF2) No Yes -
05 Quick Stop active (OFF3) No Yes -
06 Switching on inhibited active Yes No -
07 Alarm present Yes No -
08 Deviation, setpoint/actual speed No Yes -
09 Control request Yes No -
10 Maximum speed reached Yes No -
11 I, M, P limit reached No Yes -
13 Alarm motor overtemperature No Yes -
14 Motor rotates forwards Yes No -
15 Alarm drive converter overload No Yes -