Technical data

List of Parameters
Parameters
1-325
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: The power (P) for point 1 on the Y coordinate of the flow characteristic is saved in p3320. Unit: %
Dependency: Refer to: p3321
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 1 on the X coordinate of the flow characteristic is saved in p3321. Unit: %
Dependency: Refer to: p3320
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The power (P) for point 2 on the Y coordinate of the flow characteristic is saved in p3322. Unit: %
Dependency: Refer to: p3323
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 2 on the X coordinate of the flow characteristic is saved in p3323. Unit: %
Dependency: Refer to: p3322
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3320[0...n] Fluid flow machine P = f(n), Y coordinate: P flow1 %, point 1 / Fluid flow mach Y1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 25.00
p3321[0...n] Fluid flow machine P = f(n), X coordinate: n flow1 %, point 1 / Fluid flow mach X1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 0.00
p3322[0...n] Fluid flow machine P = f(n), Y coordinate: P flow2 %, point 2 / Fluid flow mach Y2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 50.00
p3323[0...n] Fluid flow machine P = f(n), X coordinate: n flow2 %, point 2 / Fluid flow mach X2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 25.00