Technical data

Parameters
List of Parameters
1-326
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: The power (P) for point 3 on the Y coordinate of the flow characteristic is saved in p3324. Unit: %
Dependency: Refer to: p3325
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 3 on the X coordinate of the flow characteristic is saved in p3325. Unit: %
Dependency: Refer to: p3324
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The power (P) for point 4 on the Y coordinate of the flow characteristic is saved in p3326. Unit: %
Dependency: Refer to: p3327
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: The speed (n) for point 4 on the X coordinate of the flow characteristic is saved in p3327. Unit: %
Dependency: Refer to: p3326
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3324[0...n] Fluid flow machine P = f(n), Y coordinate: P flow3 %, point 3 / Fluid flow mach Y3
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 77.00
p3325[0...n] Fluid flow machine P = f(n), X coordinate: n flow3 %, point 3 / Fluid flow mach X3
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 50.00
p3326[0...n] Fluid flow machine P = f(n), Y coordinate: P flow4 %, point 4 / Fluid flow mach Y4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 92.00
p3327[0...n] Fluid flow machine P = f(n), X coordinate: n flow4 %, point 4 / Fluid flow mach X4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Data set: DDS, p0180
Units group: - Unit selection: -
Min Max Factory setting
0.00 100.00 75.00