Technical data

Parameters
List of Parameters
1-414
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: Sets the signal source of minuend X1 and subtrahend X2 of instance SUB 1 of the subtractor.
Index: [0] = Minuend X1
[1] = Subtrahend X2
Description: Display parameter for the difference Y = X1 - X2 of instance SUB 1 of the subtractor.
Description: Setting parameter for the run-time group in which instance SUB 1 of the subtractor is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance SUB 1 within the run-time group set in p20108.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source of the factors X0, X1, X2, X3 of instance MUL 0 of the multiplier.
Index: [0] = Factor X0
[1] = Factor X1
[2] = Factor X2
[3] = Factor X3
p20106[0...1] CI: SUB 1 inputs / SUB 1 inputs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0
r20107 CO: SUB 1 difference Y / SUB 1 difference Y
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - -
p20108 SUB 1 run-time group / SUB 1 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
5 9999 9999
p20109 SUB 1 run sequence / SUB 1 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Data set: -
Units group: - Unit selection: -
Min Max Factory setting
0 32000 250
p20110[0...3] CI: MUL 0 inputs / MUL 0 inputs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Data set: -
Units group: - Unit selection: -
Min Max Factory setting
- - 0