Technical data

List of Parameters
Parameters
1-43
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Description: Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
Note: The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers
are identical (p0010 = 2).
When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.
Description: Displays the type of power unit found.
Value: 2: MICROMASTER 440
3: MICROMASTER 411
4: MICROMASTER 410
5: MICROMASTER 436
6: MICROMASTER 440 PX
7: MICROMASTER 430
100: SINAMICS S
101: SINAMICS S (value)
102: SINAMICS S (combi)
112: PM220 (SINAMICS G120)
113: PM230 (SINAMICS G120)
114: PM240 (SINAMICS G120)
115: PM250 (SINAMICS G120)
116: PM260 (SINAMICS G120)
118: SINAMICS G120 Px
120: PM340 (SINAMICS S120)
133: SINAMICS G120C
150: SINAMICS G
200: SINAMICS GM
250: SINAMICS SM
260: SINAMICS SM120
300: SINAMICS GL
350: SINAMICS SL
400: SINAMICS DCM
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
p0201[0...n] Power unit code number / PU code no
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(2) Scaling: - Data set: PDS
Units group: - Unit selection: -
Min Max Factory setting
0 65535 0
r0203[0...n] Actual power unit type / PU actual type
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Data set: PDS
Units group: - Unit selection: -
Min Max Factory setting
2 400 -